Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | CM 4 x IO-Link ST |
| IO-Link ports | 4; all 4 simultaneously controllable |
| Supported modes | IO-Link, DI, and DQ |
| IO-Link protocols | IO-Link 1.0 and IO-Link 1.1 |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC; 20.5 V lower limit when IO-Link is used |
| Minimum cycle time | 2 ms; dynamic, depending on user data length |
Applications
- IO-Link device communication: Communicates with IO-Link devices through 4 simultaneously controllable IO-Link ports.
- Digital signal operation: Supports digital input (DI) and digital output (DQ) operation; DQ output current is limited to 100 mA per channel.
Key Features
- IO-Link master ports: 4 IO-Link ports, all 4 simultaneously controllable; IO-Link protocol 1.0 and 1.1 are supported.
- Supported operating modes: IO-Link and DI modes are supported. DQ mode is supported with a maximum of 100 mA per channel.
- Supply voltage: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC. The lower limit is 20.5 V when IO-Link is used.
- IO-Link data and timing: Transmission rates are 4.8 kBaud (COM1), 38.4 kBaud (COM2), and 230.4 kBaud (COM3). Minimum cycle time is 2 ms, dynamic depending on user data length.
- Diagnostics and protection: The module has reverse polarity protection, short-circuit protection, wire-break detection, supply-voltage monitoring, group error diagnostics, and diagnostic LEDs.
- Installation and dimensions: Port types A and B are supported; port type B uses 24 V DC via an external terminal. Dimensions are 15 mm width, 73 mm height, and 58 mm depth.
Frequently Asked Questions
1. How many IO-Link ports does the Siemens 6AG1137-6BD00-2BA0 have?
It has 4 IO-Link ports, and all 4 can be controlled simultaneously.
2. Which IO-Link protocols does this module support?
It supports IO-Link protocol 1.0 and IO-Link protocol 1.1.
3. What supply voltage does the module require?
The rated supply voltage is 24 V DC. The permissible range is 19.2 V to 28.8 V DC; 20.5 V is the lower limit when IO-Link is used.
4. What diagnostics are available?
It supports supply-voltage monitoring, wire-break detection, short-circuit detection, group error diagnostics, and diagnostic LEDs.