Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | F-RQ 1×24 V DC/24 … 230 V AC/5 A |
| Relay outputs | 1; 2 NO contacts |
| Rated supply voltage | 24 V |
| Permissible DC supply range | 20.4 V to 28.8 V |
| Load voltage | 24 V DC and 24 to 230 V AC |
| Resistive-load switching capacity, max. | 5 A |
| Backplane bus power consumption | 100 mW |
| Diagnostics | Yes; green/red DIAG LED and green channel-status LED |
| Permissible potential difference | 250 V AC (reinforced insulation) |
| Conformal coating | Yes |
Applications
- Digital input control: The relay output can control a digital input.
Key Features
- Relay output: 1 relay output with 2 NO contacts; the output can control a digital input.
- Load voltage and capacity: Load voltage: 24 V DC and 24 to 230 V AC. Switching capacity with resistive load, max.: 5 A.
- Supply and power: Rated supply voltage: 24 V; permissible DC range: 20.4 V to 28.8 V. Power consumption from the backplane bus: 100 mW.
- Diagnostics and status: Diagnostics function: Yes. Status indication includes a green/red DIAG LED and a green channel-status LED.
- Isolation: Potential separation is provided between channels and the backplane bus, and between channels and the electronics power supply. Permissible potential difference: 250 V AC with reinforced insulation.
- Installation and coating: Overall width: 20 mm. The module has conformal coating and supports horizontal or vertical installation with specified output-current limits.
Frequently Asked Questions
1. What output configuration does the 6AG1136-6RA00-2BF0 have?
It has 1 relay output with 2 NO contacts.
2. What load voltage does this relay output module support?
It supports 24 V DC and 24 to 230 V AC load voltage.
3. What is the maximum resistive-load switching capacity?
The maximum switching capacity with resistive load is 5 A.
4. What diagnostics are available?
The module has a diagnostics function, a green/red DIAG LED, and a green channel-status LED.