6AG1136-6DB00-2CA0

Siemens 6AG1136-6DB00-2CA0 SIPLUS F-DQ module with 4 fail-safe 24 VDC transistor outputs, 2 A rated current, diagnostics, and 24 V supply. Request a model-specific quote.

Product Code
6AG1136-6DB00-2CA0
Dimensions
8.8 × 6.5 × 3.8 cm
Weight
0.072 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type F-DQ 4x24VDC HF
Digital outputs 4; transistor; parameterizable
Output voltage, rated 24 V DC
Output current, rated 2 A per channel
Supply voltage 24 V DC; permissible range 20.4 V to 28.8 V
Current consumption 75 mA; without load
Module current, max. 6 A; note derating data in the manual
Diagnostics Diagnostics function and diagnostic alarm; RUN, ERROR, PWR, channel-status, channel-diagnostics, and module-diagnostics LEDs
Fail-safe performance Up to PL e (ISO 13849); up to SIL 3 (IEC 61508)
Firmware update Possible

Applications

  1. Digital input control: The digital output can control a digital input according to IEC 61131-2, type 2.
  2. Fail-safe output control: The module provides fail-safe digital output control up to PL e according to ISO 13849 and up to SIL 3 according to IEC 61508.

Key Features

  1. Fail-safe digital outputs: 4 parameterizable transistor outputs with 24 V rated output voltage and 2 A rated current per channel.
  2. Output protection and detection: Short-circuit protection, overload protection, open-circuit detection, and inductive shutdown voltage limitation to typ. 2*47V.
  3. Switching capacity: Maximum current is 2 A per channel and 6 A per module; derating data in the manual applies.
  4. Supply and consumption: Rated supply voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V; current consumption is 75 mA without load.
  5. Diagnostics and status LEDs: Diagnostics, diagnostic alarms, RUN, ERROR, PWR, channel-status, channel-diagnostics, and module-diagnostics LEDs are supported.
  6. Isolation and cabling: Channels are isolated from the backplane bus; maximum cable length is 1 000 m shielded or 500 m unshielded.

Frequently Asked Questions

1. How many digital outputs does 6AG1136-6DB00-2CA0 have?

It has 4 parameterizable fail-safe digital transistor outputs.

2. What supply voltage does the module use?

The rated supply voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V.

3. What output current is available?

The rated output current is 2 A per channel. The maximum current is 6 A per module; derating data in the manual applies.

4. Does the module provide diagnostics?

Yes. It has a diagnostics function, diagnostic alarms, and RUN, ERROR, PWR, channel-status, channel-diagnostics, and module-diagnostics LEDs.

5. What cable lengths are supported?

The maximum cable length is 1 000 m for shielded cable and 500 m for unshielded cable.

Send Inquiry