6AG1136-6AA00-2CA1

Siemens 6AG1136-6AA00-2CA1 SIPLUS F-AI module with 4 fail-safe analog current inputs, 0 to 20 mA and 4 mA to 20 mA ranges, diagnostics, and 24 V supply. Request a model-specific quote.

Product Code
6AG1136-6AA00-2CA1
Dimensions
7.8 × 7 × 2.5 cm
Weight
0.066 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type F-AI 4xI 0(4)..20mA 2-/4-wire HF
Analog input channels 4
Supported input ranges 0 to 20 mA; 4 mA to 20 mA
Resolution with overrange max. 16 bit
Supply voltage 24 V DC; permissible range 19.2 V to 28.8 V
Input connection 2-wire and 4-wire transducers
Diagnostics Supply-voltage monitoring, wire break, short circuit, diagnostic alarm

Applications

  1. Fail-safe current measurement: Measures 0 to 20 mA and 4 mA to 20 mA signals from 2-wire and 4-wire transducers.
  2. Input diagnostics: Monitors supply voltage and detects wire breaks and short circuits on analog inputs.

Key Features

  1. Fail-safe analog inputs: 4 analog inputs support current measurement with 2-wire and 4-wire transducers.
  2. Supported current ranges: Rated input ranges are 0 to 20 mA and 4 mA to 20 mA, with 125 Ω input resistance for each range.
  3. Resolution and timing: Resolution with overrange is max. 16 bit; parameterizable integration time is 20 / 16,667 ms.
  4. Diagnostics: Diagnostics include supply-voltage monitoring, wire-break and short-circuit detection, diagnostic alarms, and channel status LEDs.
  5. Supply and encoder output: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V. The encoder supply provides 300 mA max. total current of all encoders/channels.
  6. Installation and dimensions: Horizontal installation supports -30 °C to 60 °C, with the stated spacing-module condition for 70 °C. Dimensions are 15 mm × 73 mm × 58 mm.

Frequently Asked Questions

1. How many analog inputs does 6AG1136-6AA00-2CA1 have?

It has 4 analog inputs for current measurement.

2. Which current signal ranges are supported?

It supports 0 to 20 mA and 4 mA to 20 mA rated input ranges.

3. What transducer connections are supported?

It supports 2-wire and 4-wire transducers for current measurement.

4. What diagnostics are available?

It provides supply-voltage monitoring, wire-break detection, short-circuit detection, diagnostic alarms, and LED indications.