Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | AI 8xRTD/TC 2-wire HF |
| Analog input channels | 8 |
| Resolution | Up to 16 bit including sign |
| Supply voltage | 24 V DC; 19.2 V to 28.8 V permissible range |
| Voltage input ranges | -1 V to +1 V; -250 mV to +250 mV; -50 mV to +50 mV; -80 mV to +80 mV |
| Input resistance | 1 MΩ for listed voltage, thermocouple, resistance thermometer, and resistor ranges |
| Connection | 2-wire; BU type A0, A1 |
| Diagnostics | Wire break, overflow/underflow, group error, supply-voltage monitoring, diagnostic alarms |
| Conversion time | 180 / 60 / 50 ms per channel |
| Operating temperature | -40 °C to 60 °C horizontal; -40 °C to 50 °C vertical |
Applications
- Temperature measurement: Measures temperature using RTD and thermocouple inputs.
- Resistance measurement: Measures resistance with two-wire connections across supported resistance ranges.
- Voltage measurement: Measures voltage using supported input ranges.
- Input diagnostics: Monitors input wiring, limit values, supply voltage, group errors, and channel status.
Key Features
- 8 RTD/TC 2-wire inputs: Product type designation: AI 8xRTD/TC 2-wire HF with 8 analog inputs.
- Supported signal ranges: Voltage ranges include -1 V to +1 V, -250 mV to +250 mV, -50 mV to +50 mV, and -80 mV to +80 mV; resistance and thermocouple ranges are also supported.
- 16-bit resolution: Resolution with overrange is up to 16 bit including sign.
- 24 V DC supply: Rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V and reverse polarity protection.
- Channel diagnostics: Diagnostics include wire-break and overflow/underflow detection channel by channel, group error, supply-voltage monitoring, and diagnostic alarms.
- SIPLUS protection and installation: The module has conformal coating, supports BU type A0, A1, and measures 15 mm wide, 73 mm high, and 58 mm deep.
Frequently Asked Questions
1. How many analog inputs does the 6AG1134-6JF00-2CA1 have?
It has 8 analog inputs for RTD/TC 2-wire signals.
2. Which voltage ranges does this module support?
It supports -1 V to +1 V, -250 mV to +250 mV, -50 mV to +50 mV, and -80 mV to +80 mV.
3. What resolution does the module provide?
It provides up to 16 bit including sign.
4. Which BaseUnits support the 2-wire connection?
The 2-wire connection uses BU type A0, A1 BaseUnits.
5. What diagnostics should be verified before inquiry?
Verify wire-break and overflow/underflow detection channel by channel, group error, supply-voltage monitoring, diagnostic alarms, and LED indications.