Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | AI 2xU/I 2-/4-wire HS |
| Analog input channels | 2 differential inputs |
| Voltage input ranges | 0 to +10 V; 1 V to 5 V; -10 V to +10 V; -5 V to +5 V |
| Current input ranges | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution with overrange | max. 16 bit |
| Cycle time, all channels | min. 125 μs |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Connection variants | 2-wire and 4-wire; BU type A0, A1 |
| Ambient temperature, horizontal installation | -40 °C to 60 °C; +70 °C with spacing modules or configured slots to the left and right |
Applications
- Analog signal acquisition: Measures voltage and current signals through 2 differential analog input channels.
Key Features
- Analog input channels: 2 differential analog inputs; 2 channels for current measurement and 2 channels for voltage measurement.
- Supported input ranges: Voltage: 0 to +10 V, 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V. Current: 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
- Resolution and timing: Resolution with overrange: max. 16 bit. Cycle time for all channels: min. 125 μs; conversion time per channel: 10 μs.
- Supply and protection: Rated supply voltage: 24 V DC, permissible range 19.2 V to 28.8 V, with reverse polarity protection. Current consumption: 39 mA without sensor supply.
- Diagnostics and isolation: Channel diagnostics, diagnostic alarm, limit value alarm, wire-break and short-circuit diagnostics, group error, overflow/underflow, and electrical isolation between channels, the backplane bus, and the electronics power supply.
- Connection and installation: Supports 2-wire and 4-wire connections with BU type A0, A1. Width: 15 mm; height: 73 mm; depth: 58 mm; weight approx. 32 g.
Frequently Asked Questions
1. How many analog inputs does 6AG1134-6HB00-2DA1 have?
It has 2 differential analog inputs, with 2 channels for current measurement and 2 channels for voltage measurement.
2. Which voltage and current ranges does the module support?
Voltage ranges are 0 to +10 V, 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V. Current ranges are 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
3. What resolution and cycle time are available?
Resolution with overrange is max. 16 bit. Cycle time for all channels is min. 125 μs, and conversion time per channel is 10 μs.
4. Which BaseUnits and connection variants are supported?
2-wire and 4-wire connections are supported with BU type A0, A1.