6AG1134-6HB00-2CA1

Siemens 6AG1134-6HB00-2CA1 SIPLUS analog input module with 2 differential channels, 0 to 20 mA and voltage ranges, 24 V supply. Request a model-specific quote.

Product Code
6AG1134-6HB00-2CA1
Dimensions
7.7 × 6.8 × 2.5 cm
Weight
0.042 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type AI 2xU/I 2-/4-wire HF
Analog inputs 2 differential inputs
Voltage input ranges 0 to +10 V; 1 V to 5 V; -10 V to +10 V; -5 V to +5 V
Current input ranges 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA
Resolution Up to 16 bit including sign
Supply voltage 24 V DC; 19.2 V to 28.8 V permissible
BaseUnits BU type A0, A1
Diagnostics Channel diagnostics; wire break; short circuit; limit value; overflow/underflow
Installation temperature -40 °C to 60 °C horizontal; -40 °C to 50 °C vertical

Applications

  1. Voltage and current measurement: Measures voltage and current signals through its 2 differential analog inputs.
  2. Channel diagnostics: Provides wire-break, short-circuit, supply-voltage, limit-value, overflow, and underflow diagnostics.

Key Features

  1. Analog inputs: 2 differential analog inputs support voltage and current measurement.
  2. Input ranges: Voltage ranges include 0 to +10 V, 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V. Current ranges include 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
  3. Resolution and conversion: Resolution with overrange is up to 16 bit including sign. Parameterizable integration time ranges from 67.5 ms to 0.625 ms.
  4. Supply and encoder current: Rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V. Encoder output current is max. 20 mA, with max. 50 mA per channel for < 10 s in two-wire operation.
  5. Diagnostics and isolation: The module provides channel diagnostics, wire-break detection for 4 mA to 20 mA, channel-by-channel short-circuit detection, and isolation between channels and the backplane bus.
  6. Installation and dimensions: It is suitable for BU type A0, A1 and supports horizontal installation from -40 °C to 60 °C. Dimensions are 15 mm × 73 mm × 58 mm.

Frequently Asked Questions

1. How many analog inputs does the 6AG1134-6HB00-2CA1 have?

It has 2 differential analog inputs, with 2 inputs for current measurement and 2 inputs for voltage measurement.

2. Which signal ranges does this analog input module support?

Voltage ranges are 0 to +10 V, 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V. Current ranges are 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.

3. What supply voltage does the module require?

The rated supply voltage is 24 V DC, with a permissible range of 19.2 V to 28.8 V.

4. Which BaseUnits and connections are supported?

The module supports BU type A0 and A1 for both 2-wire and 4-wire connections.

Send Inquiry