Technical Summary
| Parameter | Value |
|---|---|
| Digital input channels | 4 |
| Rated input voltage | 230 V AC |
| Signal 0 input voltage | 0 V AC to 40 V AC |
| Signal 1 input voltage | 74 V AC to 264 V AC |
| BaseUnit | BU type B1 |
| PROFINET R1 IM operation | Yes |
| Supply voltage | 230 V AC |
| Module diagnostics | Green/red DIAG LED |
| Backplane bus isolation | Yes |
Key Features
- Digital inputs: 4 parameterizable digital inputs with a rated input voltage of 230 V AC.
- Input signal ranges: Signal 0: 0 V AC to 40 V AC; signal 1: 74 V AC to 264 V AC.
- Connection and BaseUnit: 1-wire, 2-wire, and 3-wire connections use BU type B1; 4-wire connection uses BU type B1 plus a potential distributor module.
- Diagnostics indication: Green PWR LED, green channel status LEDs, and a green/red DIAG LED for module diagnostics.
- Electrical separation: Channels are electrically separated from the backplane bus; isolation is tested with 2 545 V DC/2 s (routine test).
- Operating conditions: Based on 6ES7131-6FD01-0BB1, with conformal coating and a temperature range of -40…+70 °C.
Frequently Asked Questions
1. How many digital inputs does the 6AG1131-6FD01-7BB1 have?
It has 4 parameterizable digital inputs.
2. What AC input signal ranges does this module support?
Signal 0 is 0 V AC to 40 V AC, and signal 1 is 74 V AC to 264 V AC.
3. Which BaseUnit is used for the module connections?
BU type B1 is used for 1-wire, 2-wire, and 3-wire connections. A 4-wire connection uses BU type B1 plus a potential distributor module.