| Parameter | Value |
|---|---|
| Module type | DI 8x24VAC/48VUC BA |
| Digital inputs | 8 |
| Rated supply voltage (DC) | 48 V |
| Permissible supply voltage (DC) | 40.8 V to 57.6 V |
| Rated supply voltage (AC) | 48 V; 24 V/48 V; 50 Hz/60 Hz |
| Permissible supply voltage (AC) | 40.8 V to 52.8 V |
| Signal 0 input voltage | AC/DC < 10 V |
| Signal 1 input voltage | AC > 14 V, DC > 34 V |
| Input current for signal 1, typ. | 3.5 mA |
| BaseUnit | BU type U0 |
| Address space per module, max. | 1 byte |
Applications
- Digital signal acquisition: The module acquires digital signals through its 8 digital inputs, including signals from 2-wire sensors.
Key Features
- 8 digital inputs: The module has 8 digital inputs with P-reading input and an IEC 61131 type 1 input characteristic curve.
- 48 V AC/DC signal levels: The rated supply value is 48 V DC or 48 V AC. Signal 0 is AC/DC < 10 V; signal 1 is AC > 14 V or DC > 34 V.
- Module diagnostics: Diagnostics include supply-voltage monitoring, encoder power-supply monitoring, diagnostic alarms, readable diagnostic information, and group error.
- Status indication: A green PWR LED monitors supply voltage, green LEDs display channel status, and a green/red DIAG LED indicates module diagnostics.
- BU type U0 connection: BU type U0 is used for 1-wire and 2-wire connections. 3-wire and 4-wire connections require BU type U0 plus a Potential distributor module.
- SIPLUS environmental design: The module has conformal coating and a -40…+70 °C temperature range. It is based on 6ES7131-6CF00-0AU0 and has a 1.5 W typical power loss.
Frequently Asked Questions
1. What input type and channel count does the 6AG1131-6CF00-7AU0 have?
It has 8 digital inputs with P-reading input and an IEC 61131 type 1 input characteristic curve.
2. What signal levels does this digital input module support?
For signal 0, the input voltage is AC/DC < 10 V. For signal 1, it is AC > 14 V or DC > 34 V.
3. Which BaseUnit is required for the connection?
BU type U0 is used for 1-wire and 2-wire connections. 3-wire and 4-wire connections require BU type U0 plus a Potential distributor module.
4. What diagnostics are available?
The module supports diagnostic alarms, readable diagnostic information, supply-voltage monitoring, encoder power-supply monitoring, and group error. It has green PWR and channel-status LEDs plus a green/red DIAG LED.