Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | DI 8×24 VDC SRC BA |
| Digital inputs | 8 |
| Input type | Sourcing |
| Input voltage, rated | 24 V DC |
| Input delay | 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms, plus 30 to 500 μs depending on line length |
| Supply voltage, permissible | 19.2 V to 28.8 V DC |
| Input current for signal "1", typ. | 6 mA |
| BaseUnit | BU type A0 |
| PROFINET R1 IM operation | Yes |
| Isolation between channels and backplane bus | Yes |
| Conformal coating | -40…+70 °C |
Applications
- Digital signal acquisition: Acquires digital signals through 8 sourcing inputs with parameterizable input delay and supply-voltage diagnostics.
Key Features
- Digital input channels: 8 parameterizable sourcing inputs with a 24 V DC rated input voltage and IEC 61131 type 1 input characteristic.
- Signal ranges: Signal "0": 30 V to -5 V; signal "1": -11 V to -30 V, with reference potential L+.
- Input timing: Parameterizable input delay: 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms, plus 30 to 500 μs depending on line length.
- Diagnostics: Supply-voltage monitoring, diagnostic alarms, readable diagnostic information, green PWR and channel LEDs, and a green/red DIAG LED.
- Supply and protection: Rated supply voltage: 24 V DC; permissible range: 19.2 V to 28.8 V DC; reverse polarity protection: Yes.
- BaseUnit and installation: Suitable for BU type A0. 3-wire connection requires BU type A0 with AUX terminals or a potential distributor module; 4-wire connection requires BU type A0 + Potential distributor module.
Frequently Asked Questions
1. How many digital inputs does Siemens 6AG1131-6BF61-7AA0 have?
It has 8 parameterizable sourcing digital inputs.
2. What input voltage and signal ranges does this module support?
The rated input voltage is 24 V DC. Signal "0" is 30 V to -5 V, and signal "1" is -11 V to -30 V, with reference potential L+.
3. What diagnostics are available?
The module provides supply-voltage monitoring, diagnostic alarms, readable diagnostic information, a green PWR LED, green channel LEDs, and a green/red DIAG LED.
4. Which BaseUnit and connection variants should be verified?
BU type A0 is suitable. A 3-wire connection requires BU type A0 with AUX terminals or a potential distributor module; a 4-wire connection requires BU type A0 + Potential distributor module.