Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | PM240-2 |
| Design | FSD |
| Low-overload power | 30 kW |
| High-overload power | 22 kW |
| Input | 380-480 V 3 AC +10/-20%, 47-63 Hz |
| Maximum output current | 90 A |
| Output current with high overload | 45 A |
| Protection | IP20 |
| Cooling | Internal air cooling |
| Operating conditions | -20…+50 °C |
| Lifecycle | Active Product |
Key Features
- Drive type and design: PM240-2 converter, FSD design, based on 6SL3210-1PE26-0AL0.
- Overload power: Low overload: 30 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s. High overload: 22 kW at 200% for 3 s, 150% for 57 s, and 100% for 240 s.
- Input and filtering: 380-480 V 3 AC +10/-20%, 47-63 Hz input with an integrated Class A mains filter.
- Output current: Maximum output current: 90 A. Output current without overload and with low overload: 60 A; with high overload: 45 A.
- Protection and installation: IP20 protection, internal air cooling, 472 x 200 x 237 mm dimensions (H x W x D), without CU and operating unit.
- Braking and firmware condition: Integrated braking chopper; released as of CU FW version V4.7 HF8.
Frequently Asked Questions
1. What are the low- and high-overload power ratings?
Low overload is 30 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s. High overload is 22 kW at 200% for 3 s, 150% for 57 s, and 100% for 240 s.
2. What input supply does the 6AG1210-1PE26-2AL0 use?
The input is 380-480 V 3 AC +10/-20% at 47-63 Hz.
3. What is included in the specified configuration?
The configuration has an integrated Class A mains filter and braking chopper. It is without CU and operating unit.