Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | PM240-2 |
| Power version | FSB 7.5 kW |
| Input | 380-480 V 3 AC +10/-10%, 47-63 Hz |
| Maximum output current | 27 A |
| Low-overload power | 7.5 kW |
| High-overload power | 5.5 kW |
| Pulse frequency | 4 kHz |
| Protection | IP20 |
| Cooling | Internal air cooling |
| Braking chopper | Integrated |
| Configuration exclusion | Without CU and operating unit |
Applications
- Variable-frequency power conversion: The converter provides AC input and variable output voltage from 0% to 95% of the input voltage, with a 4 kHz pulse frequency.
Key Features
- Drive power and overload ratings: Low overload: 7.5 kW at 150% for 3 s, 110% for 57 s and 100% for 240 s. High overload: 5.5 kW at 200% for 3 s, 150% for 57 s and 100% for 240 s.
- AC input and output: Input: 380-480 V 3 AC +10/-10%, 47-63 Hz. Maximum output current: 27 A; output current without overload and with low overload: 18 A; with high overload: 13.2 A.
- Integrated braking chopper: The unfiltered converter has an integrated braking chopper. Mains filter: not present.
- Protection and monitoring: It has IP20 protection, undervoltage, overvoltage, overload, ground-fault, short-circuit and stall protection, plus motor and converter temperature monitoring.
- Installation and cooling: Design: FSB. Dimensions: 291 x 100 x 165 mm (H x W x D). Cooling method: internal air cooling; cooling air flow: 0.0092 m3/s.
- Conformal coating and lifecycle: The unit has conformal coating and is an Active Product. It is released as of CU FW version V4.7 HF8 and is supplied without CU and operating unit.
Frequently Asked Questions
1. What is the low-overload power of the 6AG1210-1PE21-2UL0?
Low-overload power is 7.5 kW: 150% for 3 s, 110% for 57 s and 100% for 240 s.
2. What input supply does this PM240-2 converter use?
The input is 380-480 V 3 AC +10/-10% at 47-63 Hz.
3. What output current can the converter provide?
Maximum output current is 27 A. Output current with low overload is 18 A, and with high overload it is 13.2 A.
4. Does the converter include a braking chopper and mains filter?
It has an integrated braking chopper and is without a mains filter.
5. What is included in the configuration?
It is supplied without CU and operating unit. Request a model-specific quote to verify the required configuration.