6AG1210-1PE18-2UL1

Siemens 6AG1210-1PE18-2UL1 SIPLUS PM240-2 converter with 3 kW low-overload power, IP20 protection, integrated braking chopper, and FSA design. Request a model-specific quote.

Product Code
6AG1210-1PE18-2UL1
Dimensions
16.5 × 7.3 × 19.6 cm
Weight
1.762 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type PM240-2
Product version FSA 3 kW
Low-overload power 3 kW
High-overload power 2.2 kW
Input supply 380–480 V 3 AC +10/-10%, 47–63 Hz
Maximum output current 11.8 A
Output voltage 0% to 95% of input voltage
Pulse frequency 4 kHz
Cooling method Internal air cooling
Protection degree IP20

Key Features

  1. Power and overload ratings: Low overload: 3 kW at 150% for 3 s, 110% for 57 s, and 100% for 240 s. High overload: 2.2 kW at 200% for 3 s, 150% for 57 s, and 100% for 240 s.
  2. Input supply: Input: 380–480 V 3 AC +10/-10%, 47–63 Hz. Input voltage type: AC; mains filter: not present.
  3. Output current and voltage: Maximum output current: 11.8 A; output current without overload: 7.7 A; output voltage: 0% to 95% of input voltage.
  4. Integrated braking chopper: The converter has an integrated braking chopper and a 4 kHz pulse frequency.
  5. Cooling, protection, and installation: Internal air cooling with 0.005 m3/s cooling air flow, IP20 protection, FSA design, and dimensions of 196 x 73 x 165 mm (H x W x D).
  6. Protective functions: Undervoltage, overvoltage, overload, ground-fault, short-circuit, stall, blocked-rotor, motor-temperature, and converter-temperature protection are provided, with parameter locking.

Frequently Asked Questions

1. What is the low-overload power of Siemens 6AG1210-1PE18-2UL1?

Low-overload power is 3 kW: 150% for 3 s, 110% for 57 s, and 100% for 240 s.

2. What input supply does the PM240-2 converter use?

The input is 380–480 V 3 AC +10/-10% at 47–63 Hz. The mains filter is not present.

3. What protection and cooling details should be checked before inquiry?

The converter has IP20 protection and internal air cooling with 0.005 m3/s cooling air flow. Confirm the FSA design and 196 x 73 x 165 mm (H x W x D) dimensions.

Send Inquiry