6BK1943-2DA00-0AA2

Siemens 6BK1943-2DA00-0AA2 POM4320 rear panel mounting has 9 heating-power outputs, 400 V and 480 V output options, and system interface. Request a model-specific quote.

Product Code
6BK1943-2DA00-0AA2
Dimensions
41.2 × 33.7 × 13 cm
Weight
0.001 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet

Product Tags

Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type POM4320 rear panel mounting (UL)
Outputs 9 digital outputs; max. 1 heating element per output
Supply voltage 400 V AC phase-to-phase
Output voltage 400 V; 480 V
Power carrying capacity per output 240 W to 7 200 W at 480 V AC
High-inrush heating element power 4 000 W max. at 480 V AC
Output current 15 A max.
Mounting Backplane mounting, vertical
Interface System interface
Output connection 3-pole push-in spring-type terminal plug
Protection IP20

Applications

  1. Heating-element control: Provides half-wave control, soft start and phase control for heating elements, with heating power setpoint input in percent.

Key Features

  1. Heating-power outputs: Has 9 digital outputs and supports up to 1 heating element per output.
  2. Output power: Output power is 400 V or 480 V; power carrying capacity per output is 240 W to 7 200 W at 480 V AC, or up to 4 000 W at 480 V AC for heating elements with high inrush current.
  3. AC supply: Rated supply is 400 V phase-to-phase AC, with 50 Hz and 60 Hz rated values.
  4. Mounting and ventilation: Uses backplane mounting in a vertical position with self-ventilation.
  5. Connection and interface: Supply connection uses a 3-pole busbar plus PE; the heating and fan output connection uses a 3-pole push-in spring-type terminal plug. The interface is a system interface.
  6. Diagnostics and protection: Provides voltage diagnostics, temperature monitoring with an NTC thermistor, fuse-blown, load-failure, Triac, rotating-field, communication, supply-voltage, line-voltage, frequency and internal-temperature diagnostics. Protection is IP20.

Frequently Asked Questions

1. How many heating-power outputs does 6BK1943-2DA00-0AA2 have?

It has 9 digital outputs, with a maximum of 1 heating element per output.

2. What supply voltage does the POM4320 use?

The rated supply is 400 V AC phase-to-phase, with rated values of 50 Hz and 60 Hz.

3. What output power is supported per channel?

Power carrying capacity per output is 240 W to 7 200 W at 480 V AC. For heating elements with high inrush current, the maximum is 4 000 W at 480 V AC.

4. How is the module mounted and connected?

It uses vertical backplane mounting. The heating and fan output connection is a 3-pole plug with a push-in spring-type terminal; the supply connection is a 3-pole busbar plus PE.

Send Inquiry