6ES7522-5EH00-0AB0

Siemens 6ES7522-5EH00-0AB0 SIMATIC S7-1500 digital output module with 16 transistor channels, 24 V, 48 V, or 125 V output voltage. Request a model-specific quote.

Product Code
6ES7522-5EH00-0AB0
Dimensions
15.1 × 15.1 × 4.7 cm
Weight
0.33 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Digital output type Transistor
Number of digital outputs 16
Rated DC output voltage 24 V; 48 V, 125 V
Rated signal "1" output current 0.5 A
Maximum current per module 8 A
Maximum switching frequency with resistive load 25 Hz
Output delay 5 ms maximum for "0" to "1" and "1" to "0"
Power consumption from backplane bus 2 W
Potential separation Between channels in groups of 1 and between channels and backplane bus
Front connector Screw terminals or push-in; ordered separately

Applications

  1. Safety-oriented load-group shutdown: Supports the safety-oriented shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d according to EN ISO 13849-1:2015.

Key Features

  1. Digital output channels: 16 parameterizable transistor outputs, current-sinking and current-sourcing, arranged in groups of 1.
  2. Output voltage: Rated DC output values: 24 V, 48 V, and 125 V; rated AC output values: 24 V and 48 V at 50 – 60 Hz.
  3. Output current: Rated signal "1" output current: 0.5 A; permissible maximum range: 0.6 A. Maximum current is 0.5 A per channel, 0.5 A per group, and 8 A per module.
  4. Switching performance: Maximum switching frequency is 25 Hz with resistive load, 0.5 Hz with inductive load, and 10 Hz with lamp load. Output delay is maximum 5 ms for both "0" to "1" and "1" to "0".
  5. Diagnostics and status: RUN, ERROR, MAINT, channel status, and module diagnostics indication LEDs are provided. Substitute values are connectable; diagnostic alarm, supply-voltage monitoring, wire-break, short-circuit, and group-error functions are not available.
  6. Isolation and connection: Channels are electrically isolated from each other in groups of 1 and from the backplane bus. The front connector with screw terminals or push-in connection must be ordered separately.

Frequently Asked Questions

1. What type of outputs does the Siemens 6ES7522-5EH00-0AB0 have?

It has 16 parameterizable transistor digital outputs with current-sinking and current-sourcing capability.

2. Which output voltage values are supported?

The rated DC output values are 24 V, 48 V, and 125 V. The rated AC output values are 24 V and 48 V at 50 – 60 Hz.

3. What current limits apply to the outputs?

The rated signal "1" output current is 0.5 A, with a permissible maximum range of 0.6 A. The maximum current is 0.5 A per channel, 0.5 A per group, and 8 A per module.

4. Is the front connector included with the module?

It is without a front connector; the screw-terminal or push-in front connector must be ordered separately.

Send Inquiry