6ES7232-4HD50-0XB0

Siemens 6ES7232-4HD50-0XB0 SB 1232 analog output module with 4 AO, 14-bit DAC, ±10 V, 0–20 mA, and 4–20 mA outputs. Request a model-specific quote.

Product Code
6ES7232-4HD50-0XB0
Dimensions
8.2 × 3.4 × 7.9 cm
Weight
0.028 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type SB 1232, AQ 4x 14 bit
Analog outputs 4; Current or voltage
Output ranges -10 V to +10 V; 0 to 20 mA; 4 mA to 20 mA
Resolution 14 bit; Voltage: 14 bit; Current: 13 bit
Rated supply voltage 24 V DC
Permissible supply voltage 20.4 V to 28.8 V DC
Load impedance, voltage outputs 1 000 Ω min.
Load impedance, current outputs 600 Ω max.
Diagnostics Supply voltage monitoring, wire break, short-circuit, diagnostic alarm
Protection IP20

Applications

  1. Analog output control: Provides analog voltage or current output signals through 4 configurable analog output channels.

Key Features

  1. Analog output channels: 4 analog outputs; each channel supports current or voltage.
  2. Supported output ranges: Voltage: -10 V to +10 V; current: 0 to 20 mA or 4 mA to 20 mA.
  3. Resolution: 14 bit maximum resolution with overrange, including sign; current resolution: 13 bit.
  4. Supply voltage: Rated supply: 24 V DC; permissible range: 20.4 V to 28.8 V DC.
  5. Diagnostics: Diagnostics function and diagnostic alarm; monitoring of supply voltage, wire break, and short-circuit.
  6. Protection and dimensions: IP20 protection; packaging dimensions: 82.00 x 34.00 x 79.00 mm.

Frequently Asked Questions

1. How many analog outputs does Siemens 6ES7232-4HD50-0XB0 have?

It has 4 analog outputs, with current or voltage output supported.

2. Which signal ranges are supported?

The supported ranges are -10 V to +10 V, 0 to 20 mA, and 4 mA to 20 mA.

3. What resolution does the module provide?

Maximum resolution with overrange is 14 bit including sign; voltage resolution is 14 bit and current resolution is 13 bit.

4. What diagnostics are available?

Diagnostics include supply voltage monitoring, wire-break detection, short-circuit detection, and a diagnostic alarm.

5. What supply voltage does this module require?

The rated supply is 24 V DC, with a permissible range of 20.4 V to 28.8 V DC.