6ES7231-5QF50-0XB0

Siemens 6ES7231-5QF50-0XB0 is an SM 1231 TC analog input module with 8 thermocouple inputs, 24 V supply, ±80 mV range, and diagnostics. Request a model-specific quote.

Product Code
6ES7231-5QF50-0XB0
Dimensions
15 × 4.7 × 11 cm
Weight
0.171 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type SM 1231, AI 8×16 bit TC
Analog inputs 8; Thermocouples
Supported thermocouple types J, K, T, E, R & S, B, N, C, TXK/XK(L)
Rated voltage input range -80 mV to +80 mV
Input resistance ≥ 10 MOhm
Supply voltage 24 V DC rated; 20.4 V to 28.8 V permissible
Resolution with overrange 15 bit; + sign
Measurement principle integrating
Isolation tested with 707 V DC (type test)
Protection IP20

Applications

  1. Temperature measurement: Supports temperature measurement with adjustable degrees Celsius or degrees Fahrenheit and parameterizable temperature compensation.

Key Features

  1. 8 thermocouple inputs: Provides 8 analog thermocouple inputs and supports types J, K, T, E, R, S, B, N, C, and TXK/XK(L).
  2. Input ranges: Supports voltage input and a rated voltage range of -80 mV to +80 mV; current, resistance thermometer, and resistance input ranges are not supported.
  3. Supply and consumption: Has a 24 V DC rated supply with a permissible range of 20.4 V to 28.8 V, typical current consumption of 15 mA, and typical backplane bus consumption of 40 mA at 5 V DC.
  4. Resolution and measurement: Uses integrating measurement with 15-bit resolution with overrange, including sign; integration time is parameterizable.
  5. Diagnostics and isolation: Has readable diagnostics, diagnostic alarms, supply-voltage monitoring, wire-break detection, a DIAG LED, and potential separation between analog inputs and the electronics power supply.

Frequently Asked Questions

1. How many thermocouple channels does 6ES7231-5QF50-0XB0 have?

It has 8 analog thermocouple inputs.

2. Which thermocouple types does the module support?

It supports J, K, T, E, R & S, B, N, C, and TXK/XK(L).

3. What supply voltage does the module require?

The rated supply voltage is 24 V DC, with a permissible range of 20.4 V to 28.8 V.

4. What resolution and measurement principle does it use?

It uses integrating measurement and provides 15-bit resolution with overrange, including sign.

5. What diagnostics are available?

It has readable diagnostics, diagnostic alarms, supply-voltage monitoring, wire-break detection, and a DIAG LED.