6ES7222-5HH50-0XB0

Siemens 6ES7222-5HH50-0XB0 SIMATIC S7-1200 G2 SM 1222 digital output module with 16 relay outputs, 24 V supply, and 2 A rating. Request a model-specific quote.

Product Code
6ES7222-5HH50-0XB0
Dimensions
15 × 4.7 × 11 cm
Weight
0.217 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type SM 1222, DQ 16x relay/2 A
Digital outputs 16
Output voltage, DC 5 V DC to 30 V DC
Output voltage, AC 5 V AC to 250 V AC
Maximum resistive-load switching capacity 2 A
Rated supply voltage 24 V DC
Output delay, maximum 10 ms for “0” to “1” and 10 ms for “1” to “0”
Channel grouping 8
Backplane-bus potential separation Yes; 1500 V AC (type test)
Protection rating IP20

Key Features

  1. Digital output type: SM 1222, DQ 16x relay/2 A with 16 relay outputs.
  2. Output voltage ranges: Rated output voltage: 5 V DC to 30 V DC or 5 V AC to 250 V AC.
  3. Output capacity: Maximum switching capacity with resistive load: 2 A; lamp load: 30 W with DC and 200 W with AC.
  4. Supply voltage: Rated supply voltage: 24 V DC, with a permissible range of 20.4 V DC to 28.8 V DC.
  5. Diagnostics and isolation: Diagnostics function, diagnostic alarm, supply-voltage monitoring, DIAG LED, and output-status LED are available. Digital outputs have relay potential separation between channels in groups of 8 and 1500 V AC type-test separation from the backplane bus.
  6. Timing and protection: Maximum output delay is 10 ms for both “0” to “1” and “1” to “0” with resistive load. Short-circuit protection is not included and must be provided externally.

Frequently Asked Questions

1. How many relay outputs does the Siemens 6ES7222-5HH50-0XB0 have?

It has 16 relay outputs, arranged in groups of 8.

2. What output voltage ranges does this module support?

It supports 5 V DC to 30 V DC and 5 V AC to 250 V AC as rated output-voltage ranges.

3. What is the output switching capacity?

The maximum switching capacity is 2 A with a resistive load, 30 W with a DC lamp load, and 200 W with an AC lamp load.

4. What diagnostics are available?

The module has a diagnostics function, diagnostic alarm, supply-voltage monitoring, a DIAG LED, and an LED for output status.

5. Is short-circuit protection included?

No. Short-circuit protection must be provided externally.