6ES7231-5QF32-0XB0

Siemens 6ES7231-5QF32-0XB0 SM 1231 analog input module with 8 thermocouple channels, ±80 mV range, 24 V supply, and diagnostics. Request a model-specific quote.

Product Code
6ES7231-5QF32-0XB0
Dimensions
10.7 × 9 × 5.8 cm
Weight
0.191 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SM 1231, AI 8×16 bit TC
Analog input channels 8; Thermocouples
Supported thermocouple types J, K, T, E, R & S, B, N, C, TXK/XK(L)
Rated voltage input range -80 mV to +80 mV
Rated supply voltage 24 V DC
Maximum resolution 15 bit; + sign
Typical current consumption 40 mA
Diagnostics Alarms, readable diagnostics, supply-voltage monitoring, wire-break detection
Protection degree IP20

Applications

  1. Thermocouple temperature measurement: Acquires temperature signals from supported J, K, T, E, R, S, B, N, C and TXK/XK(L) thermocouples.

Key Features

  1. Analog input channels: 8 analog inputs for thermocouples.
  2. Supported thermocouples: Supports types J, K, T, E, R & S, B, N, C, and TXK/XK(L).
  3. Voltage input range: Rated voltage input range: -80 mV to +80 mV; input resistance ≥1 MOhm.
  4. Supply and consumption: Rated supply voltage: 24 V DC; typical current consumption: 40 mA; typical power loss: 1.5 W.
  5. Resolution and conversion: Maximum resolution with overrange is 15 bit; + sign. The measurement principle is integrating, and measured-value smoothing is parameterizable.
  6. Diagnostics and protection: Includes alarms, readable diagnostics, supply-voltage monitoring, wire-break detection, input-status and maintenance LEDs, and IP20 protection.

Frequently Asked Questions

1. How many thermocouple inputs does 6ES7231-5QF32-0XB0 have?

It has 8 analog thermocouple inputs.

2. Which thermocouple types and voltage range are supported?

It supports J, K, T, E, R & S, B, N, C, and TXK/XK(L), with a rated voltage input range of -80 mV to +80 mV.

3. What diagnostics are available on this module?

It has alarms, readable diagnostics, supply-voltage monitoring, wire-break detection, input-status and maintenance LEDs.

Send Inquiry