6ES7231-5PD32-0XB0

Siemens 6ES7231-5PD32-0XB0 SM 1231 RTD module with 4 resistance thermometer inputs, 24 V supply, 15-bit resolution, and diagnostics. Request a model-specific quote.

Product Code
6ES7231-5PD32-0XB0
Dimensions
11.2 × 9 × 6 cm
Weight
0.191 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type SM 1231, AI 4×16 bit RTD
Analog input channels 4; Resistance thermometer
Rated supply voltage 24 V DC
Supported resistance ranges 150 Ω, 300 Ω, 600 Ω
Temperature measurement units Degrees Celsius/degrees Fahrenheit
Resolution with overrange 15 bit; + sign
Diagnostics Supply-voltage monitoring, wire break, alarms, readable diagnostics
Protection degree IP20

Key Features

  1. RTD input module: Product type designation: SM 1231, AI 4×16 bit RTD.
  2. Four RTD inputs: Has 4 analog inputs for resistance thermometers, including Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, and LG-Ni1000.
  3. Resistance ranges: Supports 150 Ω, 300 Ω, and 600 Ω resistance ranges.
  4. Resolution and conversion: Resolution with overrange: 15 bit; + sign. Measurement principle: integrating. Integration time is not parameterizable.
  5. Diagnostics: Has alarms, readable diagnostics, diagnostic alarms, supply-voltage monitoring, wire-break detection, and LEDs for input status and maintenance.
  6. Supply and protection: Rated supply voltage: 24 V DC. Typical current consumption: 40 mA; typical power loss: 1.5 W. Protection degree: IP20.

Frequently Asked Questions

1. How many RTD inputs does the 6ES7231-5PD32-0XB0 have?

It has 4 analog inputs for resistance thermometers.

2. Which resistance thermometers are supported?

Supported types include Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, and LG-Ni1000.

3. What supply voltage does the module require?

The rated supply voltage is 24 V DC.

4. What diagnostics are available?

It has supply-voltage monitoring, wire-break detection, alarms, readable diagnostics, and LEDs for input status and maintenance.

Send Inquiry