6ES7223-1PL32-0XB0

Siemens 6ES7223-1PL32-0XB0 SM 1223 digital I/O module with 16 inputs, 16 relay outputs, 24 V DC supply, and IP20 protection. Request a model-specific quote.

Product Code
6ES7223-1PL32-0XB0
Dimensions
11 × 8.8 × 8.5 cm
Weight
0.319 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SM 1223, DI 16×24 V DC, DQ 16x relay
Digital inputs 16, in groups of 2
Relay outputs 16, in groups of 4
Input voltage 24 V DC; signal 0: 5 V DC at 1 mA; signal 1: 15 V DC at 2.5 mA
Output voltage 5 V DC to 30 V DC; 5 V AC to 250 V AC
Switching capacity 2 A with resistive load
Supply voltage 24 V DC; 20.4 V to 28.8 V permissible range
Backplane bus current 180 mA max. at 5 V DC
Diagnostics Diagnostic alarm and LEDs for input and output status
Potential separation 1 500 V AC for 1 minute between outputs and backplane bus
Protection IP20

Applications

  1. Digital signal acquisition: Provides 16 digital inputs for acquiring 24 V DC signals.
  2. Relay output control: Provides 16 relay outputs for switching loads up to 2 A with a resistive load.

Key Features

  1. Digital I/O channels: Has 16 digital inputs and 16 relay outputs. Inputs are arranged in groups of 2; outputs are arranged in groups of 4.
  2. 24 V DC inputs: Input rated value is 24 V DC. Signal 0 is 5 V DC at 1 mA; signal 1 is 15 V DC at 2.5 mA.
  3. Relay output switching: Relay outputs support 5 V DC to 30 V DC or 5 V AC to 250 V AC. Switching capacity is up to 2 A with a resistive load.
  4. Supply and power: Rated supply voltage is 24 V DC, with a permissible range from 20.4 V to 28.8 V. Typical power loss is 10 W.
  5. Diagnostics and isolation: Has diagnostic alarms and LEDs for input and output status. Output channels are relay-separated, with 1 500 V AC for 1 minute between outputs and the backplane bus.
  6. Mounting and protection: Maximum installation values are 16 up to 40 °C in all mounting positions, 16 up to 50 °C for horizontal installation, and IP20 protection.

Frequently Asked Questions

1. How many digital inputs and relay outputs does the 6ES7223-1PL32-0XB0 have?

It has 16 digital inputs and 16 relay outputs. Inputs are in groups of 2, and outputs are in groups of 4.

2. What input signals does this module support?

The input rated value is 24 V DC. Signal 0 is 5 V DC at 1 mA, and signal 1 is 15 V DC at 2.5 mA.

3. What output voltage and switching capacity are supported?

Output voltage is 5 V DC to 30 V DC or 5 V AC to 250 V AC. Switching capacity is up to 2 A with a resistive load.

4. What diagnostics does the module provide?

It has a diagnostic alarm and LEDs for the status of the inputs and outputs.

Send Inquiry