Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | DQ 4×24 V DC/2 A ST |
| Digital outputs | 4 |
| Output type | Source output (PNP, current-sourcing) |
| Rated output voltage | 24 V DC |
| Rated output current per channel | 2 A |
| Supply voltage range | 19.2 V to 28.8 V DC |
| Maximum current per module | 8 A |
| Short-circuit protection | Yes; Electronic |
| BaseUnit | BU type A0 |
| Module diagnostics | Yes |
Applications
- Digital output control: Controls digital outputs through 4 parameterizable source outputs.
- Redundant load control: Supports parallel switching of two outputs for redundant control of a load.
- Digital input control: Supports controlling a digital input.
Key Features
- Digital outputs: 4 parameterizable source outputs (PNP, current-sourcing), with output type according to IEC 61131, type 2.
- Output performance: Rated output voltage: 24 V DC. Rated output current for signal "1": 2 A; maximum current per module: 8 A.
- Output switching: Maximum switching capacity is 2 A with resistive load and 10 W on lamp load. Maximum switching frequency is 100 Hz with resistive load, 2 Hz with inductive load, and 10 Hz on lamp load.
- Diagnostics and protection: The module has module diagnostics, open-circuit detection, supply-voltage monitoring, group error, electronic short-circuit protection, and diagnostic alarm.
- Supply and connection: Rated supply voltage: 24 V DC, with a permissible range from 19.2 V to 28.8 V and reverse polarity protection. BU type A0 supports 1-wire and 2-wire connections.
- Isolation and timing: Channels are isolated from the backplane bus. Output delay with resistive load is 50 μs from "0" to "1" and 100 μs from "1" to "0", typical and maximum.
Frequently Asked Questions
1. What output type does 6ES7132-6BD20-0BA0 use?
It uses 4 parameterizable source outputs (PNP, current-sourcing).
2. How many digital outputs and what current do they support?
It has 4 digital outputs, with a rated output current of 2 A per channel and a maximum current of 8 A per module.
3. What supply voltage does the module support?
The rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V and reverse polarity protection.
4. Which diagnostics are available?
It has module diagnostics, supply-voltage monitoring, wire-break and short-circuit diagnostics, group error, open-circuit detection, and diagnostic alarm.