Product Overview

Technical Summary

Parameter Value
IO-Link ports 4
IO-Link protocols 1.0 and 1.1
Operating modes IO-Link, DI, DQ
DQ maximum 100 mA
Rated supply voltage 24 V DC
Rated load voltage 2L+ 24 V DC
Diagnostics Diagnostic alarm; readable diagnostic information; channel-by-channel wire break and short circuit
Port connections Port type A via 3-core cable; Port type B
Firmware version V1.2.5

Key Features

  1. 4 IO-Link ports: Has 4 IO-Link ports, all 4 simultaneously controllable, with IO-Link protocol 1.0 and 1.1 support.
  2. IO-Link data and transmission: Supports 4.8 kBaud (COM1), 38.4 kBaud (COM2), and 230.4 kBaud (COM3); process data is 32 byte per port and per module for input and output.
  3. Operating modes: Supports IO-Link, DI, and DQ; DQ has a maximum of 100 mA.
  4. Diagnostics: Has diagnostic alarms and readable diagnostic information, with channel-by-channel wire-break and short-circuit diagnostics.
  5. 24 V supply and protection: Rated supply voltage and load voltage 2L+ are 24 V DC; the module has reverse polarity and short-circuit protection.
  6. Connections and installation: Supports Port type A via 3-core cable and Port type B; unshielded cable length is maximum 20 m.

Frequently Asked Questions

1. How many IO-Link ports does Siemens 6ES7147-4JD00-0AB0 have?

It has 4 IO-Link ports, all 4 simultaneously controllable.

2. Which operating modes does this module support?

It supports IO-Link, DI, and DQ modes. DQ has a maximum of 100 mA.

3. What IO-Link protocols and transmission rates are supported?

It supports IO-Link protocol 1.0 and 1.1, with 4.8 kBaud (COM1), 38.4 kBaud (COM2), and 230.4 kBaud (COM3).

4. What diagnostics are available?

It has diagnostic alarms and readable diagnostic information, including channel-by-channel wire-break and short-circuit diagnostics.