Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Digital output channels | 16 |
| Load voltage, rated DC | 24 V |
| Load voltage, permissible range | 20.4 V to 57.6 V |
| Output current for signal "1", rated | 0.5 A |
| Switching frequency with resistive load, max. | 10 Hz |
| Required front connector | 40-pin |
| Isolation between channels and backplane bus | Yes; Optocoupler |
| Product lifecycle | Product cancellation |
Applications
- Digital input control: The outputs can control a digital input.
Key Features
- Digital output channels: 16 digital outputs with isolated solid-state relays and potential separation between channels in groups of 1.
- Supply and output current: Load voltage: 24 V rated DC, permissible range 20.4 V to 57.6 V. Output current for signal "1": 0.5 A rated value.
- Output protection and diagnostics: Short-circuit protection: No; to be provided externally. Diagnostics function, diagnostic alarm, readable diagnostic information, and LED indicators are available; functions are parameterizable where stated.
- Switching performance: Output delay with resistive load: 6 ms from "0" to "1" and 3 ms from "1" to "0". Switching frequency: 10 Hz with resistive load and 0.5 Hz with inductive load.
- Connection and isolation: Required front connector: 40-pin. Isolation is tested with 1 500 V AC, and channels are separated from the backplane bus by an optocoupler.
- Dimensions and weight: Dimensions: 40 mm width, 125 mm height, and 120 mm depth. Weight: approximately 260 g.
Frequently Asked Questions
1. How many digital outputs does 6ES7322-5GH00-0AB0 have?
It has 16 digital outputs with isolated solid-state relays.
2. What load voltage does this digital output module support?
The rated DC load voltage is 24 V, with a permissible range from 20.4 V to 57.6 V.
3. What is the rated output current for signal "1"?
The rated output current for signal "1" is 0.5 A.
4. Which front connector is required?
A 40-pin front connector is required.
5. Does it include short-circuit protection?
It is without short-circuit protection; this must be provided externally.