Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Digital output channels | 16 |
| Rated load voltage | 24 V DC |
| Output current for signal "1", rated | 0.5 A |
| Permissible load voltage range | 20.4 V to 28.8 V |
| Short-circuit protection | Yes; Electronic |
| Required front connector | 20-pin |
| Output isolation | Between channels in groups of 8; from the backplane bus by optocoupler |
| Output delay with resistive load | "0" to "1": 100 μs max.; "1" to "0": 500 μs max. |
| Total output current per group | 4 A max. with horizontal installation up to 40 °C; 3 A max. with horizontal installation up to 60 °C; 2 A max. with vertical installation up to 40 °C |
Applications
- Digital output control: Controls digital inputs.
- Redundant load control: Supports parallel switching of two outputs for redundant control of a load.
Key Features
- Digital outputs: 16 digital outputs with 0.5 A rated output current for signal "1".
- Load voltage: Rated load voltage: 24 V DC; permissible range: 20.4 V to 28.8 V.
- Output protection: Electronic short-circuit protection; short-circuit response threshold: 1 A.
- Electrical isolation: Digital outputs are isolated between channels in groups of 8 and from the backplane bus by optocouplers.
- Connection and dimensions: Required front connector: 20-pin. Dimensions: 40 mm width, 125 mm height, and 120 mm depth.
Frequently Asked Questions
1. How many digital outputs does 6ES7322-1BH01-0AA0 have?
It has 16 digital outputs.
2. What load voltage and output current does this module use?
The rated load voltage is 24 V DC, and the rated output current for signal "1" is 0.5 A.
3. Does the module provide short-circuit protection?
Yes. It has electronic short-circuit protection, with a typical response threshold of 1 A.
4. What connector is required for this configuration?
A 20-pin front connector is required.