Technical Summary
| Parameter | Value |
|---|---|
| Product type | TP2200 Comfort PRO |
| Display operation | Projective-capacitive touch screen |
| Display resolution | 1 920 pixel horizontal x 1 080 pixel vertical |
| Industrial Ethernet interfaces | 2; 2 ports (switch) + independent port |
| USB interfaces | 2; USB 2.0 |
| Supported protocols | PROFINET, PROFINET IO, IRT, PROFIBUS, EtherNet/IP, MPI, TCP/IP, DHCP, SNMP, DCP, LLDP, MRP, MODBUS |
| Supply voltage | 24 V DC rated; 19.2 V to 28.8 V permissible |
| Mounting | Support arm, vertical; landscape possible |
| Protection | IP65 at the front and rear |
Applications
- Touch-based S7 input: Uses 40 direct keys as touch buttons configured as S7 input I/O.
- Industrial Ethernet communication: Communicates using PROFINET, including PROFINET IO and IRT, through the industrial Ethernet interfaces.
- PROFIBUS communication: Communicates through the MPI/PROFIBUS DP interface and supports PROFIBUS.
Key Features
- Touch display: TFT touch screen with projective-capacitive touch operation, 1 920 pixel horizontal resolution, 1 080 pixel vertical resolution, and 16 777 216 colors.
- Network interfaces: 2 industrial Ethernet interfaces with 2 switch ports and 1 independent port; 1 combined RS 422/485 interface and 2 USB 2.0 interfaces.
- Supported protocols: Supports PROFINET, PROFINET IO, IRT, PROFIBUS, EtherNet/IP, MPI, TCP/IP, DHCP, SNMP, DCP, LLDP, HTTP, HTTPS, HTML, XML, CSS, Active X, MRP, and MODBUS.
- Support-arm installation: Support-arm mounting in a vertical position; landscape mounting is possible, portrait mounting is not, and the maximum permissible inclination without external ventilation is 35°.
- DC supply: Rated supply voltage: 24 V DC. Permissible supply range: 19.2 V to 28.8 V; rated current consumption: 1.8 A; typical active power input: 44 W.
- Protection and diagnostics: IP65 protection at the front and rear, front Enclosure Type 4 and Type 4x, and diagnostic information readable by an S7 controller.
Frequently Asked Questions
1. What interfaces does Siemens 6AV2124-0XC24-0AX0 provide?
It has 2 industrial Ethernet interfaces with 2 switch ports and 1 independent port, 1 combined RS 422/485 interface, 2 USB 2.0 interfaces, and 2 SD card slots.
2. Which protocols does this Comfort Panel support?
It supports PROFINET, PROFINET IO, IRT, PROFIBUS, EtherNet/IP, MPI, TCP/IP, DHCP, SNMP, DCP, LLDP, MRP, and MODBUS.
3. How is the panel mounted and powered?
It uses support-arm mounting in a vertical position. The rated supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V.