Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Display | 18.5 in widescreen TFT |
| Resolution | 1 366 pixel × 768 pixel |
| Touch screen | Analog-resistive |
| Direct keys | 40 for S7 input I/O |
| Industrial Ethernet | 2 interfaces; 2 switch ports + independent port |
| Protocols | PROFINET, PROFIBUS, EtherNet/IP, MPI |
| Supply | 24 V DC; 19.2 V to 28.8 V permissible range |
| User-data memory | 24 Mbyte |
| Mounting | Vertical; portrait and landscape formats possible |
| Protection | IP65 front; IP20 rear |
Applications
- Process operator control: The panel supports operator control of the process through touch operation, onscreen keyboards, and 40 direct keys for S7 input I/O.
Key Features
- Widescreen TFT display: The display has an 18.5 in diagonal, 1 366 pixel × 768 pixel resolution, and 16 777 216 colors.
- Touch operation and direct keys: The analog-resistive touch screen supports numeric and alphanumeric onscreen keyboards, with 40 direct keys for S7 input I/O.
- Industrial Ethernet and protocols: The panel has 2 industrial Ethernet interfaces with 2 switch ports plus 1 independent port. It supports PROFINET, PROFINET IO, IRT, PROFIBUS, EtherNet/IP, MPI, TCP/IP, DHCP, SNMP, DCP, and LLDP.
- Additional interfaces and storage: It has 1 combined RS 422 / 485 interface, 2 USB 2.0 interfaces, and 2 SD card slots.
- Supply and mounting: Supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V. Mounting is vertical, with portrait and landscape formats possible; the maximum permissible angle of inclination without external ventilation is 35°.
- Front and rear protection: Protection is IP65 at the front and IP20 at the rear. The front has NEMA Enclosure Type 4 and Enclosure Type 4x.
Frequently Asked Questions
1. Which communication interfaces does the TP1900 Comfort have?
It has 2 industrial Ethernet interfaces with 2 switch ports plus 1 independent port, 1 combined RS 422 / 485 interface, 2 USB 2.0 interfaces, and 2 SD card slots.
2. Which protocols does 6AV2124-0UC02-0AX1 support?
It supports PROFINET, PROFINET IO, IRT, PROFIBUS, EtherNet/IP, MPI, TCP/IP, DHCP, SNMP, DCP, LLDP, HTTP, HTTPS, HTML, XML, CSS, Active X, JavaScript, MRP, and MODBUS.
3. What supply voltage does the panel require?
Supply is 24 V DC, with a permissible range of 19.2 V to 28.8 V.
4. How is the panel mounted and protected?
Mounting is vertical, with portrait and landscape formats possible. Protection is IP65 at the front and IP20 at the rear; the maximum permissible angle of inclination without external ventilation is 35°.