Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | KP300 Basic mono PN |
| Display | 3.6 in FSTN LCD |
| Display resolution | 240 pixel × 80 pixel |
| Function keys | 10 |
| Industrial Ethernet interfaces | 1 |
| Protocols | PROFINET; EtherNet/IP; TCP/IP; DHCP; SNMP; DCP; LLDP |
| Rated supply | 24 V DC |
| Permissible supply range | 19.2 V to 28.8 V |
| Mounting | Vertical; landscape format possible |
| Front protection | IP65 |
Key Features
- Display and operation: 3.6 in FSTN LCD display with 240 pixel horizontal and 80 pixel vertical image resolution, numeric and alphanumeric keyboard, system keys, and 10 function keys.
- PROFINET and Ethernet interfaces: 1 industrial Ethernet interface with PROFINET, EtherNet/IP, TCP/IP, DHCP, SNMP, DCP and LLDP support.
- Power supply: 24 V DC rated supply with a permissible range of 19.2 V to 28.8 V, 0.1 A rated current consumption and 3 W typical active power input.
- Mounting: Vertical mounting position; landscape-format mounting is possible. The maximum permissible angle of inclination without external ventilation is 35°.
- Front and rear protection: IP65 protection at the front and IP20 protection at the rear. Enclosure Type 4 and Enclosure Type 4x are supported at the front.
- Product status and software: Product cancellation. Configurable as of WinCC Basic V11 / STEP 7 Basic V11; contains open-source software provided free of charge.
Frequently Asked Questions
1. What display and operating elements does the KP300 Basic mono PN have?
It has a 3.6 in FSTN LCD display with 240 pixel × 80 pixel resolution, 10 function keys, system keys, and numeric and alphanumeric keyboards. The display has 4 colors and is backlit only.
2. Which network protocols and interfaces are supported?
The panel has 1 industrial Ethernet interface and supports PROFINET, EtherNet/IP, TCP/IP, DHCP, SNMP, DCP and LLDP. It does not support PROFINET IO, PROFIBUS, IRT, MPI, or USB interfaces.
3. What supply voltage does this panel require?
The rated supply is 24 V DC. The permissible supply range is 19.2 V to 28.8 V.
4. How can the panel be mounted?
The mounting position is vertical, and landscape-format mounting is possible. Rack mounting, wall mounting/direct mounting, and portrait-format mounting are not supported. The maximum permissible angle of inclination without external ventilation is 35°.