6SL3210-1KE32-1AF1

6SL3210-1KE32-1AF1 SINAMICS G120C drive with 6 DI, 2 DO, 1 AI, 1 AO, PROFINET and 380-480 V 3 AC input. Request a model-specific quote.

Product Code
6SL3210-1KE32-1AF1
Dimensions
74.5 × 46.9 × 38.5 cm
Weight
66 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Input phases 3 AC
Line voltage 380 … 480 V +10 % -20 %
Line frequency 47 … 63 Hz
Standard digital inputs 6
Digital outputs 1 relay changeover contact and 1 transistor
Analog inputs 1 differential input, 10 bit
Analog outputs 1 non-isolated output
Communication PROFINET, EtherNet/IP
Rated power 110.00 kW (LO); 90.00 kW (HO)
Maximum output current 328.00 A
Frame size FSF
Degree of protection IP20 / UL open type

Applications

  1. Drive control: Supports V/f linear, square-law and parameterizable control, V/f with flux current control (FCC), V/f ECO linear and square-law control, and sensorless vector control.

Key Features

  1. I/O interface: 6 standard digital inputs, 1 fail-safe digital input, 2 digital outputs, 1 differential analog input and 1 non-isolated analog output.
  2. Communication: Integrated PROFINET and EtherNet/IP communication.
  3. Input supply: 3 AC input, 380 … 480 V +10 % -20 % and 47 … 63 Hz.
  4. Drive output: Rated power: 110.00 kW (LO) or 90.00 kW (HO); maximum output current: 328.00 A.
  5. Connections and mounting: Screw-type terminals are provided for the line side, motor end, DC link and PE connection. Frame size is FSF.
  6. Protection and dimensions: Degree of protection: IP20 / UL open type. Dimensions: 305 mm width and 357 mm depth; net weight: 65.50 kg.

Frequently Asked Questions

1. What I/O does the 6SL3210-1KE32-1AF1 have?

It has 6 standard digital inputs, 1 fail-safe digital input, 2 digital outputs, 1 differential analog input and 1 non-isolated analog output.

2. Which communication protocols are integrated?

Integrated communication is available for PROFINET and EtherNet/IP.

3. What input supply does this SINAMICS G120C drive use?

The input is 3 AC, 380 … 480 V +10 % -20 % at 47 … 63 Hz.

Send Inquiry