6SL3210-1KE23-8AP1

Siemens SINAMICS G120C converter with 18.50 kW LO output, PROFIBUS DP, 6 digital inputs and IP20 protection. Request a model-specific quote.

Product Code
6SL3210-1KE23-8AP1
Dimensions
27 × 36.5 × 16 cm
Weight
5.5 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Input phases 3 AC
Line voltage 380 … 480 V +10 % -20 %
Line frequency 47 … 63 Hz
Rated output power, LO 18.50 kW | 25.00 hp
Rated output power, HO 15.00 kW | 20.00 hp
Digital inputs 6 standard digital inputs; 1 fail-safe digital input
Analog input 1 differential input, 10 bit
Communication PROFIBUS DP
Protection IP20 / UL open type
Frame size FSC

Applications

  1. Motor control: Supports V/f control, V/f with flux current control, V/f ECO control, and sensorless vector control.

Key Features

  1. Rated output power: 18.50 kW | 25.00 hp at low overload (LO) and 15.00 kW | 20.00 hp at high overload (HO).
  2. I/O interface: 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, and 1 non-isolated analog output.
  3. Communication and safety: PROFIBUS DP communication and integrated Safe Torque Off.
  4. Input and output frequency: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Output frequency: 0 … 240 Hz for vector control and 0 … 550 Hz for V/f control.
  5. Connection and protection: Plug-in screw terminals, IP20 / UL open type, FSC frame size, and dimensions of 140 mm width × 203 mm depth.

Frequently Asked Questions

1. What output power does the 6SL3210-1KE23-8AP1 provide?

It provides 18.50 kW | 25.00 hp at low overload (LO) and 15.00 kW | 20.00 hp at high overload (HO).

2. How many I/O points does this converter have?

It has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, and 1 non-isolated analog output.

3. Which communication interface is provided?

The converter provides PROFIBUS DP communication.

4. What connections and protection are available?

It has plug-in screw terminals and IP20 / UL open type protection. Verify the required conductor cross-sections and installation details before inquiry.