Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Communication | PROFIBUS DP |
| Input | 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz |
| Rated power, low overload | 4.00 kW | 5.00 hp |
| Rated power, high overload | 3.00 kW | 4.00 hp |
| Standard digital inputs | 6 |
| Fail-safe digital inputs | 1 |
| Analog / digital inputs | 1 (Differential input) |
| Analog outputs | 1 (Non-isolated output) |
| Output frequency for vector control | 0 … 240 Hz |
| Output frequency for V/f control | 0 … 550 Hz |
| Degree of protection | IP20 / UL open type |
Key Features
- Supply and rated power: Input: 3 AC, 380 … 480 V +10 % -20 %, 47 … 63 Hz. Rated power: 4.00 kW at low overload and 3.00 kW at high overload.
- I/O configuration: The interface has 6 standard digital inputs, 1 fail-safe digital input, 1 relay changeover contact, 1 transistor output, 1 differential analog input, and 1 non-isolated analog output.
- Communication and safety: Communication: PROFIBUS DP. Safe Torque Off is integrated.
- Output control: Output frequency: 0 … 240 Hz for vector control and 0 … 550 Hz for V/f control. Supported control techniques include V/f linear / square-law / parameterizable, V/f with flux current control (FCC), V/f ECO linear / square-law, and sensorless vector control.
- Connections and motor cable: Line-side, motor-end, and DC-link connections use plug-in screw terminals. Maximum shielded motor cable length: 150 m (492.13 ft).
- Mounting and protection: Frame size: FSA. Dimensions: 73 mm (2.87 in) width and 203 mm (7.99 in) depth. Degree of protection: IP20 / UL open type.
Frequently Asked Questions
1. What communication interface does 6SL3210-1KE18-8UP1 have?
It has PROFIBUS DP communication.
2. How many standard digital inputs and outputs does it have?
It has 6 standard digital inputs, 1 relay changeover contact, and 1 transistor output.
3. What analog I/O is included?
It has 1 differential analog input with 10 bit resolution and 1 non-isolated analog output.
4. What are the connection terminals?
The line-side, motor-end, and DC-link connections use plug-in screw terminals.