Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | MTP1500 Unified Comfort PRO Neutral Front |
| Display | 15.6 in widescreen TFT, 16 777 216 colors |
| Resolution | 1 366 pixel × 768 pixel |
| Touch operation | Touch screen and multi-touch screen |
| Industrial Ethernet interfaces | 2; 2 ports (switch) + independent port |
| Protocols | PROFINET, TCP/IP, DHCP, SNMP, DCP, LLDP, MRP |
| RS 422 / 485 interface | 1 combined interface |
| USB interfaces | 4; USB 3.1 Gen. 1 (type A) |
| Rated supply | 24 V DC |
| Current consumption | 0.7 A rated; 1.3 A maximum |
| Mounting | Support arm, vertical; landscape possible |
Key Features
- 15.6 in widescreen display: The TFT display has a 15.6 in screen diagonal, 1 366 pixel horizontal resolution, 768 pixel vertical resolution, and 16 777 216 colors.
- Multi-touch operator interface: The panel has a touch screen and multi-touch screen, with numeric and alphanumeric onscreen keyboards.
- PROFINET and Ethernet interfaces: It has 2 industrial Ethernet interfaces with 2 ports for the integrated switch plus an independent port. PROFINET, TCP/IP, DHCP, SNMP, DCP, LLDP, and MRP are supported; PROFINET IO protocol support is not.
- Additional interfaces: The panel has 1 combined RS 422 / 485 interface, 4 USB 3.1 Gen. 1 type A interfaces, and 2 SD card slots.
- 24 VDC supply: Rated supply is 24 V, with a permissible DC range from 19.2 V to 28.8 V. Current consumption is 0.7 A rated and 1.3 A maximum.
- Support-arm installation: Mounting is for a support arm in vertical position. Landscape mounting is possible; portrait mounting is not. The maximum permissible angle of inclination without external ventilation is 35°.
Frequently Asked Questions
1. Which network protocols does 6AV2128-3QB57-0AX0 support?
It supports PROFINET, TCP/IP, DHCP, SNMP, DCP, LLDP, and MRP. It does not support the protocol for PROFINET IO.
2. How many Ethernet ports does the panel have?
It has 2 industrial Ethernet interfaces: 2 ports for the integrated switch plus an independent port.
3. What supply voltage does the panel require?
The rated supply is 24 V DC, with a permissible range from 19.2 V to 28.8 V.
4. How is the panel mounted?
It is mounted on a support arm in vertical position. Landscape mounting is possible, while portrait mounting is not; the maximum permissible angle of inclination without external ventilation is 35°.