Product Overview

Technical Summary

Parameter Value
Product type BU type U0
Process terminals 16
Terminal type Push-in terminal
Supply voltage for P1 and P2 bus 120 V DC or 277 V AC
Supply voltage for AUX bus 120 V DC or 277 V AC
Supply voltage for process terminals 120 V DC or 277 V AC
Current carrying capacity up to 60 °C 10 A max.
Potential group New potential group
Potential separation Between backplane bus and supply voltage: Yes

Key Features

  1. BaseUnit type: BU20-P16+A0+2D with BU type U0 for SIMATIC ET 200SP.
  2. Process terminals: 16 process terminals are provided for connection to an I/O module.
  3. Connection and AUX terminals: Push-in terminals; AUX terminals: 0.
  4. Potential group: Forms a new potential group and does not continue a potential group from the left.
  5. Supply voltage: For P1 and P2 bus, AUX bus, and process terminals: 120 V DC or 277 V AC. External protection for power supply lines is required.
  6. Installation dimensions: Width: 20 mm; height: 117 mm; depth: 35 mm. Horizontal installation ambient temperature: -30 °C to 60 °C; vertical installation: -30 °C to 50 °C.

Frequently Asked Questions

1. How many process terminals does Siemens 6ES7193-6BP00-0DU0 have?

It has 16 process terminals for connection to an I/O module.

2. What terminal type does this BaseUnit use?

It uses Push-in terminals and has 0 AUX terminals.

3. What supply voltages are supported?

For the P1 and P2 bus, AUX bus, and process terminals, the source lists 120 V DC and 277 V AC. External protection for power supply lines is required.