6AG2231-5PD32-1XB0

Siemens 6AG2231-5PD32-1XB0 SIPLUS S7-1200 SM 1231 RTD module with 4 resistance-thermometer inputs, 24 V supply and diagnostics. Request a model-specific quote.

Product Code
6AG2231-5PD32-1XB0
Dimensions
10.9 × 8.8 × 5.6 cm
Weight
0.207 kg
Lifecycle
Active Product
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SM 1231, AI 4×16 bit RTD
Analog inputs 4; Resistance thermometer
Rated supply voltage 24 V DC
Typical input current 40 mA
Backplane bus current, typical 80 mA at 5 V DC
Supported resistance range 150 Ω, 300 Ω, 600 Ω
Resolution with overrange 15 bit; + sign
Measurement principle integrating
Interference voltage suppression 85 dB at 50 / 60 / 400 Hz
Diagnostics Alarms, readable diagnostics, supply-voltage monitoring and wire-break monitoring
Isolation test 750 V DC (type test) and according to EN 50155 (routine test)
Protection degree IP20

Applications

  1. Resistance-temperature measurement: Measures temperature with supported Pt, Ni and Cu resistance thermometers.

Key Features

  1. 4 analog RTD inputs: SM 1231 module with 4 analog inputs for resistance thermometers.
  2. Supported resistance thermometers: Supports Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100 and LG-Ni1000.
  3. Rated supply and consumption: Rated supply voltage: 24 V DC. Typical input current: 40 mA; typical backplane bus current at 5 V DC: 80 mA.
  4. Resolution and conversion: Resolution with overrange: 15 bit; + sign. Measurement principle: integrating. Integration time is not parameterizable.
  5. Diagnostics and isolation: Has alarms, readable diagnostics, diagnostic alarm, supply-voltage monitoring, wire-break monitoring and input-status and maintenance LEDs. Isolation is tested with 750 V DC (type test).
  6. Rail-based installation: Requires a front connector. Dimensions: 45 mm × 100 mm × 75 mm. Protection degree: IP20.

Frequently Asked Questions

1. What input type does the 6AG2231-5PD32-1XB0 use?

It has 4 analog inputs for resistance thermometers.

2. Which resistance thermometers are supported?

It supports Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100 and LG-Ni1000.

3. What supply does the module require?

The rated supply voltage is 24 V DC.

4. What diagnostics are available?

It has alarms, readable diagnostics, supply-voltage monitoring, wire-break monitoring and LEDs for input status and maintenance.

5. What connection and mounting details should be verified?

The module requires a front connector and has dimensions of 45 mm × 100 mm × 75 mm with IP20 protection.

Send Inquiry