Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Product type | Active backplane ST 1+12 slot |
| Backplane bus | 12 slots; active |
| Total number of slots | 13 |
| Maximum IM slots | 1 |
| Maximum PS slots | 12; maximum 2 PS per station |
| Power consumption from the backplane bus | 2 W |
| Horizontal installation temperature | -40 °C to 70 °C |
| Vertical installation temperature | -40 °C to 40 °C |
| Maximum installation altitude | 5 000 m above sea level |
| Conformal coating | Class 2 for high reliability according to EN 61086 |
Applications
- Hot swapping of S7-1500 I/O modules: The active backplane bus supports inserting S7-1500 I/O modules for hot swapping.
- ET 200MP installation: The backplane is for use in the ET 200MP with IM 155-5 PN HF from FW V4.4.1.
Key Features
- Active backplane bus: Active backplane ST 1+12 slot for inserting S7-1500 I/O modules for hot swapping.
- Slot capacity: 13 slots total; maximum 1 IM, 12 PS with maximum 2 PS per station, and 12 IO/CM/CP/TM or F-IO.
- Operating temperature: -40 °C to 70 °C for horizontal installation; -40 °C to 40 °C for vertical installation.
- System functions: Supports I&M0 to I&M3 data, isochronous mode, prioritized startup, and firmware updates.
- Conformal coating: Conformal coating for high reliability, with Class 2 according to EN 61086 and Type 1 protection according to EN 60664-3.
- Dimensions and weight: 434 mm wide, 99 mm high, 14 mm deep, with an approximate weight of 352 g.
Frequently Asked Questions
1. What is the function of the Siemens 6AG1590-0BL00-7AA0?
It is an active backplane ST 1+12 slot with a 12-slot active backplane bus for inserting S7-1500 I/O modules for hot swapping.
2. How many slots does the active backplane have?
It has 13 slots total, including a maximum of 1 IM slot and 12 PS slots; a maximum of 2 PS are permitted per station.
3. What are its installation temperature limits?
The limits are -40 °C to 70 °C for horizontal installation and -40 °C to 40 °C for vertical installation.
4. Which ET 200MP configuration is stated for this backplane?
It is for use in the ET 200MP with IM 155-5 PN HF from FW V4.4.1.
5. What is not included with the product?
The S7-1500 mounting rail and slot covers must be ordered separately.