Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Digital output type | Sink output (NPN) |
| Number of digital outputs | 8 |
| Rated supply voltage | 24 V DC |
| Permissible supply voltage | 19.2 V to 28.8 V DC |
| Rated output current, signal "1" | 0.5 A per channel |
| Maximum current per module | 4 A |
| Output delay, "0" to "1" | 300 μs maximum with resistive load |
| Output delay, "1" to "0" | 600 μs maximum with resistive load |
| Usable BaseUnit | BU type A0 |
| Diagnostic functions | Supply-voltage monitoring, group error, diagnostic alarm, and substitute values |
| Isolation | Between channels and backplane bus; tested with 707 V DC (type test) |
Applications
- Digital input control: The module can control a digital input.
- Redundant load control: Two outputs can be switched in parallel for redundant control of a load.
Key Features
- Digital output channels: 8 configurable sink outputs (NPN) with current-sinking operation; current-sourcing is not supported.
- Output current: Rated output current for signal "1": 0.5 A per channel; maximum current per module: 4 A.
- Supply voltage: Rated supply voltage: 24 V DC, with a permissible range from 19.2 V to 28.8 V DC.
- Output protection: Short-circuit protection is available. The typical response threshold is 1.5 A, and inductive shutdown voltage is typically limited to 47 V.
- Diagnostics and LEDs: Supply-voltage monitoring, group error, diagnostic alarm, substitute values, a green PWR LED, a green channel-status LED, and a green/red DIAG LED are supported.
- Installation and connection: Fits BU type A0 and has a type B mechanical coding element. Maximum cable length is 1 000 m shielded or 600 m unshielded.
Frequently Asked Questions
1. How many digital outputs does the 6ES7132-6BF61-0AA0 have?
It has 8 configurable sink outputs (NPN).
2. What supply voltage does this module use?
The rated supply voltage is 24 V DC, with a permissible range from 19.2 V to 28.8 V DC.
3. What output current is available per channel?
The rated output current for signal "1" is 0.5 A per channel, and the maximum current per channel is 0.5 A.
4. Which BaseUnit and cable lengths should be verified before ordering?
The module fits BU type A0. Maximum cable length is 1 000 m with shielded cable or 600 m with unshielded cable.