Technical Summary
| Parameter | Value |
|---|---|
| Product type | CPU 417-5H PN/DP |
| Work memory | 32 Mbyte RAM; 16 Mbyte program and 16 Mbyte data |
| Interfaces | 2 RS 485; 2 RJ 45 (Ethernet) ports; integrated switch |
| PROFINET function | PROFINET IO Controller; maximum transmission rate 100 Mbit/s |
| PROFIBUS DP masters | 2 integrated; maximum 32 connections at 12 Mbit/s |
| Power loss | 7.5 W typical |
| Installation space | 2 required slots |
| Operating temperature | -25 °C to 70 °C; at 60°C for UL/ATEX/FM and safety-related application |
Applications
- S7-400H central processing: Provides central processing for S7-400H systems.
- PROFINET IO control: Controls PROFINET IO devices as an integrated PROFINET IO Controller.
- PROFIBUS DP master communication: Communicates with PROFIBUS DP devices through the integrated DP masters.
Key Features
- CPU function: CPU 417-5H PN/DP for S7-400H with firmware version V6.0 and HW functional status 1.
- Work memory: Integrated 32 Mbyte RAM: 16 Mbyte for the program and 16 Mbyte for data; not expandable.
- Communication interfaces: 2 RS 485 interfaces with MPI/PROFIBUS DP interface type, plus 2 RJ 45 (Ethernet) ports and an integrated switch.
- PROFINET communication: PROFINET IO Controller and Open IE communication are supported; maximum transmission rate is 100 Mbit/s.
- PROFIBUS DP master: 2 integrated DP masters support up to 32 DP connections at a maximum transmission rate of 12 Mbit/s.
- Environmental design: Conformal coating with ambient temperature during operation from -25 °C to 70 °C; at 60°C for UL/ATEX/FM and safety-related application.
Frequently Asked Questions
1. What is the function of Siemens 6AG1417-5HT06-7AB0?
It is a CPU 417-5H PN/DP providing central processing for S7-400H systems.
2. How much work memory does this CPU have?
It has 32 Mbyte integrated RAM: 16 Mbyte for the program and 16 Mbyte for data. The work memory is not expandable.
3. Which communication interfaces are provided?
It has 2 RS 485 interfaces, 2 RJ 45 (Ethernet) ports, an integrated switch, MPI/PROFIBUS DP, and PROFINET IO Controller functionality.