Technical Summary
| Parameter | Value |
|---|---|
| Analog inputs | 4 |
| Analog outputs | 2 |
| Input voltage range | 0 to +10 V |
| Resistance measurement range | 0 to 10000 ohms |
| Resolution | 12 bit |
| Rated load voltage L+ | 24 V DC |
| Connection | 1x 20-pole |
| Output short-circuit protection | Yes |
| Product status | Product cancellation |
Applications
- Voltage measurement: Supports voltage measurement through 2 analog inputs and a 0 to +10 V input range.
- Resistance measurement: Supports resistance measurement through 4 analog inputs, including Pt 100 and 0 to 10000 ohms ranges.
- Analog voltage output: Provides 2 analog voltage outputs with a 0 to 10 V output range.
Key Features
- Analog inputs and outputs: Has 4 analog inputs and 2 analog outputs. Inputs support voltage, resistance thermometer, and resistance measurement; outputs provide 0 to 10 V.
- Signal ranges and resolution: Input voltage range is 0 to +10 V, with 100 kΩ input resistance. Resistance measurement supports 0 to 10000 ohms, and resolution is 12 bit.
- Supply and protection: Rated load voltage L+ is 24 V DC with reverse polarity protection. Input current is max. 80 mA from supply and load voltage L+ without load.
- Connection and installation: Has a 1x 20-pole connection. Shielded cable length is max. 100 m for the analog inputs and outputs.
- Output protection and load: Voltage outputs have short-circuit protection and a max. short-circuit current of 10 mA. Minimum load impedance is 2.5 kΩ; maximum capacitive load is 1 μF.
- Conformal coating and temperature: Has conformal coating and a temperature range of -25…+70 °C. The product is marked as Product cancellation.
Frequently Asked Questions
1. How many analog inputs and outputs does 6AG1334-0KE00-7AB0 have?
It has 4 analog inputs and 2 analog outputs.
2. Which input signals does this module support?
It supports voltage measurement from 0 to +10 V, Pt 100 measurement in the climatic range, and resistance measurement from 0 to 10000 ohms.
3. What output range and load limits apply?
The voltage output range is 0 to 10 V. Minimum load impedance is 2.5 kΩ, maximum capacitive load is 1 μF, and short-circuit current is max. 10 mA.
4. What connection and cable length does it use?
It has a 1x 20-pole connection. Shielded cable length is max. 100 m for the analog inputs and outputs.