Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SIPLUS S7-300 analog input module |
| Analog inputs | 8 |
| Supported voltage ranges | 1 V to 5 V; -10 V to +10 V; -5 V to +5 V |
| Supported current ranges | 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA |
| Resolution with overrange, max. | 16 bit |
| Integration time, parameterizable | 10/ 16.67/ 20/ 100 ms |
| Input resistance | 2 MΩ for 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V; 250 Ω for 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA |
| Backplane bus input current, max. | 130 mA from backplane bus 5 V DC |
| Isolation tested with | 500 V DC |
| Power loss, typ. | 0.6 W |
Applications
- Voltage measurement: Supports connection of signal encoders for voltage measurement.
- Current measurement: Supports current measurement with 2-wire transducers using an external transmitter and possible separate transmitter supply, and with 4-wire transducers.
Key Features
- 8 analog inputs: Provides 8 analog inputs for voltage and current measurement; thermocouple, resistance thermometer, and resistance input ranges are not supported.
- Supported signal ranges: Supports 1 V to 5 V, -10 V to +10 V, -5 V to +5 V, 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA rated input ranges.
- Resolution and integration: Resolution with overrange is max. 16 bit; parameterizable integration time is 10/ 16.67/ 20/ 100 ms.
- Diagnostics and alarms: Has parameterizable diagnostics and diagnostic alarms, readable diagnostic information, a parameterizable limit value alarm for channels 0 and 2, and a red group error SF LED.
- Isolation and channel groups: Analog inputs are not isolated between channels, are isolated from the backplane bus, and are arranged in groups of 2 for channel potential separation.
- Conformal coating and temperature range: Has conformal coating and a -25…+70 °C temperature range.
Frequently Asked Questions
1. How many analog inputs does the 6AG1331-7NF00-2AB0 have?
It has 8 analog inputs.
2. Which signal ranges does this analog input module support?
It supports 1 V to 5 V, -10 V to +10 V, -5 V to +5 V, 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA rated input ranges.
3. What diagnostics are available?
It has parameterizable diagnostics and diagnostic alarms, readable diagnostic information, a parameterizable limit value alarm for channels 0 and 2, and a red group error SF LED.