6AG1331-7NF00-2AB0

Siemens 6AG1331-7NF00-2AB0 SIPLUS analog input module with 8 AI, 16 bit resolution, voltage and current ranges, diagnostics, and 500 V DC isolation. Request a model-specific quote.

Product Code
6AG1331-7NF00-2AB0
Dimensions
13 × 15 × 4.9 cm
Weight
0.316 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SIPLUS S7-300 analog input module
Analog inputs 8
Supported voltage ranges 1 V to 5 V; -10 V to +10 V; -5 V to +5 V
Supported current ranges 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA
Resolution with overrange, max. 16 bit
Integration time, parameterizable 10/ 16.67/ 20/ 100 ms
Input resistance 2 MΩ for 1 V to 5 V, -10 V to +10 V, and -5 V to +5 V; 250 Ω for 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA
Backplane bus input current, max. 130 mA from backplane bus 5 V DC
Isolation tested with 500 V DC
Power loss, typ. 0.6 W

Applications

  1. Voltage measurement: Supports connection of signal encoders for voltage measurement.
  2. Current measurement: Supports current measurement with 2-wire transducers using an external transmitter and possible separate transmitter supply, and with 4-wire transducers.

Key Features

  1. 8 analog inputs: Provides 8 analog inputs for voltage and current measurement; thermocouple, resistance thermometer, and resistance input ranges are not supported.
  2. Supported signal ranges: Supports 1 V to 5 V, -10 V to +10 V, -5 V to +5 V, 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA rated input ranges.
  3. Resolution and integration: Resolution with overrange is max. 16 bit; parameterizable integration time is 10/ 16.67/ 20/ 100 ms.
  4. Diagnostics and alarms: Has parameterizable diagnostics and diagnostic alarms, readable diagnostic information, a parameterizable limit value alarm for channels 0 and 2, and a red group error SF LED.
  5. Isolation and channel groups: Analog inputs are not isolated between channels, are isolated from the backplane bus, and are arranged in groups of 2 for channel potential separation.
  6. Conformal coating and temperature range: Has conformal coating and a -25…+70 °C temperature range.

Frequently Asked Questions

1. How many analog inputs does the 6AG1331-7NF00-2AB0 have?

It has 8 analog inputs.

2. Which signal ranges does this analog input module support?

It supports 1 V to 5 V, -10 V to +10 V, -5 V to +5 V, 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA rated input ranges.

3. What diagnostics are available?

It has parameterizable diagnostics and diagnostic alarms, readable diagnostic information, a parameterizable limit value alarm for channels 0 and 2, and a red group error SF LED.

Send Inquiry