6AG1332-8TF01-2AB0

Siemens 6AG1332-8TF01-2AB0 is a SIPLUS S7-300 analog output module with 8 AO, 0 to 20 mA and 4 mA to 20 mA HART ranges, 24 V supply, and diagnostic functions. Request a model-specific quote.

Product Code
6AG1332-8TF01-2AB0
Dimensions
13 × 15 × 5 cm
Weight
0.268 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SIPLUS S7-300 analog output module
Analog outputs 8 AO
Current output ranges 0 to 20 mA; 4 mA to 20 mA
Rated load voltage L+ 24 V DC
Resolution with overrange 16 bit including sign, max.
Load impedance 750 Ω max. with current outputs
Connection 20-pole; two-wire actuator connection for current output
Diagnostic functions Yes
Isolation test 500 V DC
Conformal coating -25…+60 °C
Based on 6ES7332-8TF01-0AB0

Applications

  1. Firmware updating: Supports firmware update.
  2. HART auxiliary variables: Supports HART auxiliary variables.
  3. Redundancy: Supports redundancy.
  4. Local diagnostics: Provides a local diagnostic buffer with time stamping.

Key Features

  1. 8-channel analog output: Provides 8 analog outputs with current output ranges of 0 to 20 mA and 4 mA to 20 mA; the 4 mA to 20 mA range supports HART.
  2. Supply and current: Rated load voltage L+ is 24 V DC. Input current is max. 350 mA from load voltage L+ without load and max. 110 mA from the backplane bus 5 V DC.
  3. Resolution and settling time: Resolution with overrange is max. 16 bit including sign. Settling time is 0.1 ms for a resistive load and 0.5 ms for an inductive load.
  4. Diagnostics and functions: Has diagnostics, diagnostic alarms, readable diagnostic information, connectable substitute values, firmware update, HART auxiliary variables, redundancy, and a local diagnostic buffer with time stamping.
  5. Isolation and protection: Has reverse polarity protection. The analog outputs are isolated from the backplane bus, load voltage L+, and the electronics power supply; isolation is tested with 500 V DC.
  6. Connection and environmental details: Supports two-wire actuator connection for current output, max. 800 m shielded cable length, max. 750 Ω load impedance with current outputs, and conformal coating for -25…+60 °C.

Frequently Asked Questions

1. How many analog outputs does the 6AG1332-8TF01-2AB0 have?

It has 8 analog outputs.

2. Which current output ranges are supported?

It supports 0 to 20 mA and 4 mA to 20 mA. The 4 mA to 20 mA output is HART-based.

3. What supply voltage does this module use?

The rated load voltage L+ is 24 V DC.

4. What diagnostics does the module provide?

It has diagnostics, diagnostic alarms, readable diagnostic information, connectable substitute values, a red Group error SF LED, and a local diagnostic buffer with time stamping.