6AG1332-5HD01-7AB0

Siemens 6AG1332-5HD01-7AB0 SIPLUS S7-300 analog output module with 4 isolated AO, U/I ranges, diagnostics, 24 V rated supply, and 20-pole connection. Request a model-specific quote.

Product Code
6AG1332-5HD01-7AB0
Dimensions
11 × 15 × 5 cm
Weight
0.255 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Analog output channels 4
Voltage output ranges 0 to 10 V; 1 V to 5 V; -10 V to +10 V
Current output ranges 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA
Resolution with overrange Up to 12 bit; ±10 V, ±20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit
Conversion time per channel 0.8 ms
Load voltage L+ rated value 24 V DC
Connection 20-pole; four-wire voltage output; two-wire current output
Product condition Spare part; product cancellation

Applications

  1. Analog actuator output: Provides voltage output with four-wire actuator connection and current output with two-wire actuator connection.

Key Features

  1. Analog outputs: 4 analog outputs with voltage and current output ranges.
  2. Supported signal ranges: Voltage: 0 to 10 V, 1 V to 5 V, and -10 V to +10 V. Current: 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
  3. Resolution and timing: Resolution with overrange: up to 12 bit; conversion time per channel: 0.8 ms.
  4. Diagnostics and isolation: Diagnostics, diagnostic alarms, readable diagnostic information, and red group error SF LED. The channels are isolated from the backplane bus, load voltage L+, and electronics power supply.
  5. Supply and connection: Load voltage L+ rated value: 24 V DC. Connection: 20-pole; four-wire connection for voltage output and two-wire connection for current output.
  6. Installation and environmental data: Conformal coating, -25…+70 °C, and removal or insertion with the active backplane bus possible. Product cancellation.

Frequently Asked Questions

1. How many analog outputs does 6AG1332-5HD01-7AB0 have?

It has 4 analog outputs.

2. Which voltage and current ranges does the module support?

Voltage: 0 to 10 V, 1 V to 5 V, and -10 V to +10 V. Current: 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.

3. What resolution and conversion time does it provide?

Resolution with overrange is up to 12 bit, and conversion time is 0.8 ms per channel.

4. What connection and supply details should be verified?

It has a 20-pole connection, uses four-wire voltage output and two-wire current output connections, and has a 24 V DC rated load voltage L+.