6AG1332-5HB01-2AB0

Siemens 6AG1332-5HB01-2AB0 SIPLUS S7-300 module with 2 isolated analog outputs, U/I ranges, 12-bit resolution, and 24 V supply. Request a model-specific quote.

Product Code
6AG1332-5HB01-2AB0
Dimensions
13 × 15 × 5 cm
Weight
0.249 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SIPLUS S7-300 spare-part module with 2 isolated analog outputs
Analog outputs 2
Supported voltage output ranges 0 to 10 V; 1 V to 5 V; -10 V to +10 V
Supported current output ranges 0 to 20 mA; -20 mA to +20 mA; 4 mA to 20 mA
Maximum resolution 12 bit with overrange
Rated load voltage L+ 24 V DC
Maximum input current from L+ 135 mA without load
Maximum input current from backplane bus 60 mA from the 5 V DC backplane bus
Diagnostics Parameterizable diagnostics, substitute values, and diagnostic alarms; readable diagnostic information
Connection 20-pole; two-wire and four-wire voltage-output connections; two-wire current-output connections
Isolation 500 V DC test; channels isolated from backplane bus, load voltage L+, and electronics power supply
Environmental coating and temperature Conformal coating, -25…+70 °C

Applications

  1. Analog output signal control: Provides voltage and current analog output signals for connected actuators through two-wire or four-wire voltage connections and two-wire current connections.

Key Features

  1. 2 isolated analog outputs: Provides 2 analog outputs for voltage and current signals; the channels are not isolated from each other but are isolated from the backplane bus, load voltage L+, and electronics power supply.
  2. Voltage and current ranges: Supports 0 to 10 V, 1 V to 5 V, -10 V to +10 V, 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.
  3. 12-bit maximum resolution: Resolution with overrange is 12 bit; ±10 V, ±20 mA, 4 mA to 20 mA, and 1 V to 5 V provide 11 bit + sign, while 0 V to 10 V and 0 mA to 20 mA provide 12 bit.
  4. 24 V DC supply: Rated load voltage L+ is 24 V DC with reverse polarity protection; input current is 135 mA maximum from L+ without load and 60 mA maximum from the 5 V DC backplane bus.
  5. Diagnostics and parameterization: Diagnostics, substitute values, and diagnostic alarms are parameterizable; diagnostic information is readable and the group error SF LED is red.
  6. 20-pole connection and installation: Uses a 20-pole connection, supports two-wire and four-wire voltage-output actuator connections and two-wire current-output connections, and permits removal and insertion with the active backplane bus.

Frequently Asked Questions

1. How many analog outputs does the 6AG1332-5HB01-2AB0 have?

It has 2 analog outputs for voltage and current signals.

2. Which signal ranges does this module support?

Voltage ranges are 0 to 10 V, 1 V to 5 V, and -10 V to +10 V. Current ranges are 0 to 20 mA, -20 mA to +20 mA, and 4 mA to 20 mA.

3. What resolution does the module provide?

Maximum resolution with overrange is 12 bit. ±10 V, ±20 mA, 4 mA to 20 mA, and 1 V to 5 V provide 11 bit + sign; 0 V to 10 V and 0 mA to 20 mA provide 12 bit.

4. What supply voltage and connection does it use?

Rated load voltage L+ is 24 V DC, and the module uses a 20-pole connection.

5. What diagnostics and mounting details should be verified before inquiry?

Diagnostics, substitute values, and diagnostic alarms are parameterizable. Removal and insertion with the active backplane bus is possible.