Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module basis | 6ES7331-7PF11-0AB0 |
| Analog input channels | 8 |
| Supported thermocouples | Type B, E, J, K, L, N, R, S, T, U, C and TXK/TXK(L) to GOST |
| Resolution | 16 bit; Two's complement |
| Rated load voltage L+ | 24 V DC |
| Basic conversion time | up to 4 channels: 10 ms per module, over 5 channels: 190 ms per module, 8 channels: 80 ms |
| Product lifecycle | Product cancellation |
Applications
- Thermocouple signal acquisition: Acquires temperature signals from supported thermocouples through 8 analog input channels.
Key Features
- Analog inputs: 8 analog inputs for thermocouples, including types B, E, J, K, L, N, R, S, T, U, C and TXK/TXK(L) to GOST.
- Resolution and conversion: 16 bit resolution with Two's complement; integration time is parameterizable. Basic conversion time is up to 4 channels: 10 ms per module, over 5 channels: 190 ms per module, 8 channels: 80 ms.
- Thermocouple compensation: Parameterizable internal temperature compensation, external temperature compensation with Pt100 or compensations socket, and definable comparison point temperature.
- Diagnostics and alarms: Parameterizable diagnostics, diagnostic alarms per group, limit value alarms, hardware interrupts for channels 0 to 7, readable diagnostic information, and red Group error SF LED.
- Supply and isolation: Rated load voltage L+ is 24 V DC with reverse polarity protection. Analog inputs are separated from the backplane bus and electronics power supply; isolation is tested with 500 V DC.
Frequently Asked Questions
1. How many analog inputs does the Siemens 6AG1331-7PF11-4AB0 have?
It has 8 analog inputs for thermocouples.
2. Which thermocouple types does this module support?
It supports types B, E, J, K, L, N, R, S, T, U, C and TXK/TXK(L) to GOST.
3. What resolution does the 6AG1331-7PF11-4AB0 provide?
The resolution is 16 bit with Two's complement.
4. What supply voltage and isolation details should be verified?
The rated load voltage L+ is 24 V DC. The analog inputs are separated from the backplane bus and electronics power supply, with isolation tested with 500 V DC.