Product Overview

Technical Summary

Parameter Value
Module type SIPLUS S7-300 analog input module
Analog inputs 8
Measurement functions Resistance measurement and resistance thermometer measurement
Supported resistance thermometers Cu 10, Ni 100/120/200/500/1000, Pt 100/200/500/1000
Supported resistor ranges 0 to 150 ohms, 0 to 300 ohms, 0 to 600 ohms
Signal connections 2-wire without resistance correction, 3-wire, 4-wire
Resolution 16 bit with overrange; Two's complement
Basic conversion time up to 4 channels: 10 ms per module, over 5 channels: 190 ms per module, 8 channels: 80 ms
Rated load voltage 24 V DC
Input current from load voltage 240 mA max. without load
Diagnostics Parameterizable diagnostics, alarms, hardware interrupts, readable diagnostic information, red SF group error LED
Isolation Between analog inputs and backplane bus and electronics power supply; tested with 500 V DC

Applications

  1. Resistance measurement: The module performs resistance measurement using two-wire, three-wire, or four-wire signal encoder connections.
  2. Resistance thermometer measurement: The module measures resistance thermometers including Cu 10, Ni 100/120/200/500/1000, and Pt 100/200/500/1000.

Key Features

  1. 8 analog inputs: The module has 8 analog inputs for resistance measurement.
  2. Resistance measurement: Supported inputs include Cu 10, Ni 100/120/200/500/1000, Pt 100/200/500/1000, and 0 to 150/300/600 ohms.
  3. 2/3/4-wire connections: Resistance measurement supports two-wire connection without resistance correction, plus three-wire and four-wire connections.
  4. Resolution and conversion: Resolution is 16 bit with overrange and Two's complement. Basic conversion time is up to 4 channels: 10 ms per module, over 5 channels: 190 ms per module, 8 channels: 80 ms.
  5. Diagnostics: The module has parameterizable diagnostics, diagnostic and limit value alarms, hardware interrupts for channels 0 to 7, readable diagnostic information, and a red SF group error LED.
  6. Supply and isolation: Rated load voltage is 24 V DC with reverse polarity protection. Analog inputs are isolated from the backplane bus and electronics power supply; isolation is tested with 500 V DC.

Frequently Asked Questions

1. How many analog inputs does 6AG1331-7PF01-4AB0 have?

It has 8 analog inputs for resistance measurement.

2. Which resistance thermometers are supported?

It supports Cu 10, Ni 100/120/200/500/1000, and Pt 100/200/500/1000.

3. Which signal encoder connections are supported?

It supports two-wire connection without resistance correction, three-wire connection, and four-wire connection.

4. What resolution and conversion times does the module provide?

Resolution is 16 bit with overrange and Two's complement. Basic conversion time is up to 4 channels: 10 ms per module, over 5 channels: 190 ms per module, 8 channels: 80 ms.

5. What should be verified before requesting a quote?

Verify the required resistance ranges, signal encoder connection, 24 V DC supply, diagnostics configuration, and installation details.

Send Inquiry