Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Digital output channels | 8 F-DQ |
| Rated supply voltage | 24 V; 1L+ |
| Rated load voltage | 24 V; 2L+, 3L+ |
| Rated output current for signal "1" | 2 A |
| Output current range, 0 to 40 °C | 7 mA to 2 A; with horizontal installation, 1 A with vertical installation |
| Switching frequency, resistive load | 30 Hz, max. |
| Switching frequency, inductive load | 2 Hz, max. |
| Diagnostic alarm | Yes; parameterizable |
| Potential separation | Between channels; between channels and backplane bus; between channels and the electronics power supply |
| Isolation test | 500V AC for 1 min (internal voltage limiting to ±120V) |
| Product lifecycle | Product cancellation |
Applications
- Fail-safe digital output control: Controls digital output signals using F-DQ sinking-sourcing outputs with fail-safe operation.
Key Features
- Fail-safe digital outputs: 8 F-DQ digital outputs with sinking-sourcing operation up to category 4 (EN 954-1) and SIL 3 (IEC 61508).
- Supply and load voltage: Rated supply voltage: 24 V; 1L+. Rated load voltage: 24 V; 2L+, 3L+.
- Output current: Rated output current for signal "1": 2 A. Permissible range for 0 to 40 °C: 7 mA to 2 A with horizontal installation, and 1 A with vertical installation.
- Diagnostics and protection: Short-circuit protection, parameterizable diagnostic alarm, readable diagnostic information, fail-safe operation indication, and red SF group error LED.
- Electrical isolation: Digital outputs have potential separation between channels, between channels and the backplane bus, and between channels and the electronics power supply.
- Timing and connection limits: Maximum switching frequency is 30 Hz with resistive load, 2 Hz with inductive load, and 10 Hz with lamp load. Maximum cable length is 200 m.
Frequently Asked Questions
1. How many digital outputs does the 6AG1326-2BF41-2AY0 have?
It has 8 F-DQ digital outputs.
2. What output current does this module provide?
The rated output current for signal "1" is 2 A. From 0 to 40 °C, the permissible range is 7 mA to 2 A with horizontal installation, and 1 A with vertical installation.
3. What diagnostics are available?
It has a parameterizable diagnostic alarm, readable diagnostic information, fail-safe operation indication, and a red SF group error LED.
4. What cable length is supported?
The maximum cable length is 200 m for shielded and unshielded cable; 200 m applies for SIL 3, AK 6, Cat 4 with shielded cable.
5. Is the module protected against short circuits?
Yes, the digital outputs have short-circuit protection.