Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Module type | SIPLUS S7-300 F-DO spare part |
| Based on | 6ES7326-2BF41-0AB0 |
| Digital outputs | 8 fail-safe digital outputs |
| Rated supply voltage | 24 V; 1L+ |
| Rated load voltage | 24 V; 2L+, 3L+ |
| Rated output current for signal "1" | 2 A |
| Maximum output current for signal "1", 0 to 40 °C | 2 A for horizontal installation; 1 A for vertical installation |
| Maximum output current for signal "1", 40 to 60 °C | 1 A for horizontal installation |
| Diagnostic alarm | Yes; parameterizable |
| Isolation test | 500 V DC/350 V AC |
Applications
- Fail-safe digital output control: Provides fail-safe digital output control with 8 digital outputs and output-current monitoring-related diagnostics.
Key Features
- Fail-safe digital outputs: 8 digital outputs with short-circuit protection, potential separation between channels in groups of 4, and potential separation from the backplane bus and electronics power supply.
- Output rating: Output current for signal "1": 2 A rated value; permissible maximum is 2 A for horizontal installation at 0 to 40 °C and 1 A for horizontal installation at 40 to 60 °C.
- Supply and load voltage: Rated supply voltage: 24 V; 1L+. Rated load voltage: 24 V; 2L+, 3L+. Reverse polarity protection is available for the supply voltage, but not for the load voltage.
- Diagnostics: Parameterizable diagnostic alarm, readable diagnostic information, fail-safe operation indication, and red SF group-error LED indication.
- Installation and isolation: Shielded cable length up to 200 m, including 200 m for SIL 3, AK 6, Cat 4. Isolation is tested with 500 V DC/350 V AC.
- Product status and coating: Spare part with conformal coating; product cancellation.
Frequently Asked Questions
1. How many fail-safe digital outputs does 6AG1326-2BF41-2AB0 have?
It has 8 fail-safe digital outputs.
2. What are the rated supply and load voltages?
The rated supply voltage is 24 V; 1L+. The rated load voltage is 24 V; 2L+, 3L+.
3. What output current is available for signal "1"?
The rated output current is 2 A. The permissible maximum is 2 A for horizontal installation at 0 to 40 °C and 1 A for horizontal installation at 40 to 60 °C.
4. What diagnostic functions are included?
The module has a parameterizable diagnostic alarm, readable diagnostic information, fail-safe operation indication, and a red SF group-error LED.