6AG1326-1RF01-4AB0

Siemens 6AG1326-1RF01-4AB0 SIPLUS S7-300 SM 326F provides 8 fail-safe NAMUR digital inputs, 24 V DC supply, diagnostics, and 1x 40-pole connection. Request a model-specific quote.

Product Code
6AG1326-1RF01-4AB0
Dimensions
15.4 × 13.2 × 9.1 cm
Weight
0.56 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type SIPLUS S7-300 SM 326F digital input
Digital inputs 8
Input signal NAMUR
Rated supply voltage 24 V DC
Diagnostic alarm Yes; Parameterizable
Connection 1x 40-pole
Power loss, typ. 4.5 W
Product lifecycle Product cancellation

Applications

  1. Fail-safe NAMUR signal input: Provides fail-safe NAMUR input for SIMATIC S7 F-systems, with up to category 4 (EN 954-1), SIL3 (IEC 61508), and PLE (ISO 13849).

Key Features

  1. Fail-safe NAMUR digital inputs: Provides 8 digital inputs for fail-safe NAMUR signals in SIMATIC S7 F-systems.
  2. 24 V DC supply: Rated supply voltage is 24 V DC, with reverse polarity protection.
  3. NAMUR signal values: Permissible quiescent current for signal "0" is 0.35 to 1.2 mA; typical current for signal "1" is 2.1 to 7 mA.
  4. Diagnostics: Has a parameterizable diagnostic alarm, fail-safe operation indication, and red group error SF LED.
  5. Ex(i) protection and separation: Has Ex(i) protection and potential separation between channels, the backplane bus, and the electronics power supply.
  6. Connection and temperature: Has a 1x 40-pole connection and supports all mounting positions with 8 inputs up to 40 °C and up to 60 °C.

Frequently Asked Questions

1. How many digital inputs does the Siemens 6AG1326-1RF01-4AB0 have?

It has 8 digital inputs for NAMUR signals.

2. What supply voltage does this module use?

The rated supply voltage is 24 V DC.

3. What diagnostics does the module provide?

It has a parameterizable diagnostic alarm, fail-safe operation indication, and a red group error SF LED.

4. What connection is included?

The module has a 1x 40-pole connection.

Send Inquiry