Product Overview
Technical Summary
| Parameter | Value |
|---|---|
| Digital output channels | 8 isolated digital outputs |
| Load voltage | 120/230 V AC; permissible range 79 V to 264 V |
| Rated output current | 2 A |
| Output-current range, 0 to 40 °C | 10 mA to 2 A |
| Output-current range, 40 to 60 °C | 10 mA to 1 A |
| Connection | 1x 40-pole |
| Diagnostics | Parameterizable diagnostics and diagnostic alarm; red group error SF LED; green digital-output status indicators |
| Isolation | 1 500 V AC test; optocoupler separation from the backplane bus |
| Switching frequency | 10 Hz with resistive load; 0.5 Hz with inductive load |
| Total output current per group | 8 A horizontal up to 40 °C; 4 A horizontal up to 60 °C; 4 A vertical up to 40 °C |
Applications
- Digital input control: The digital outputs can control a digital input.
- Redundant load control: Two outputs can be switched in parallel for redundant control of a load.
- Motor starter control: The outputs can control motor starters up to Size 5 according to NEMA.
Key Features
- 8 isolated digital outputs: The module has 8 digital outputs with potential separation between channels and between the channels and the backplane bus.
- AC load voltage and output current: Load voltage is 120/230 V AC, with a rated output current of 2 A. For 0 to 40 °C, the permissible output-current range is 10 mA to 2 A; for 40 to 60 °C, it is 10 mA to 1 A.
- Conformal coating and temperature range: The module has conformal coating and a temperature range of 0…+60 °C.
- Diagnostics and indicators: It has parameterizable diagnostics and diagnostic alarms, with a red group error SF LED and green digital-output status indicators.
- Connection and protection: The connection is 1x 40-pole. Short-circuit protection must be provided externally with a 3.15 A / 250 V quick-response fuse.
- Switching and installation limits: Maximum switching frequency is 10 Hz with a resistive load and 0.5 Hz with an inductive load. Total output current per group is up to 8 A for horizontal installation up to 40 °C, 4 A for horizontal installation up to 60 °C, and 4 A for vertical installation up to 40 °C.
Frequently Asked Questions
1. How many digital outputs does the 6AG1322-5FF00-4AB0 have?
It has 8 isolated digital outputs.
2. What load voltage and output current does this module support?
The load voltage is 120/230 V AC. Rated output current is 2 A; the permissible range is 10 mA to 2 A from 0 to 40 °C and 10 mA to 1 A from 40 to 60 °C.
3. What connection does the module use?
It has a 1x 40-pole connection.
4. Does the module provide diagnostics?
Yes. It has parameterizable diagnostics and diagnostic alarms, a red group error SF LED, and green digital-output status indicators.
5. What should be verified before requesting a quote?
Verify the required load voltage, output-current range, installation orientation and temperature, external short-circuit fuse, total output current per group, and 1x 40-pole connection.