6AG1322-1HH01-2AA0

Siemens 6AG1322-1HH01-2AA0 SIPLUS S7-300 spare part with 16 optically isolated relay outputs, 24 V coil supply, and 2 A output current. Request a model-specific quote.

Product Code
6AG1322-1HH01-2AA0
Dimensions
13 × 15 × 5 cm
Weight
0.277 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Product type SIPLUS S7-300 digital relay output spare part
Based on 6ES7322-1HH01-0AA0
Digital outputs 16; Relays
Rated load voltage L+ 120 V DC
Rated load voltage L1 230 V AC
Rated relay-coil supply 24 V DC
Rated output current for signal "1" 2 A
Minimum load current for signal "1" 10 mA
Typical power loss 4.5 W
Switching frequency with resistive load, max. 1 Hz
Switching frequency with inductive load, max. 0.5 Hz
Operating temperature and coating -40…+70 °C; conformal coating

Applications

  1. Digital input control: The digital outputs can control a digital input.
  2. Motor-starter control: The outputs support motor starters up to Size 5 according to NEMA.

Key Features

  1. Digital relay outputs: 16 digital outputs with relay contacts; the outputs are optically isolated.
  2. Load voltage: Rated load voltage is 120 V DC or 230 V AC.
  3. Output current: Rated output current for signal "1" is 2 A, with a minimum load current of 10 mA.
  4. Relay coil supply: Rated supply voltage of relay coil L+ is 24 V DC.
  5. Channel separation: Digital outputs are electrically separated between channels in groups of 8 and from the backplane bus by optocoupler.
  6. Protection and diagnostics: Short-circuit protection, alarms, diagnostics, wire-break diagnosis, and short-circuit diagnosis are not available.

Frequently Asked Questions

1. What output type and channel count does 6AG1322-1HH01-2AA0 have?

It has 16 digital relay outputs with optically isolated channels.

2. What load voltages are supported?

The rated load voltage is 120 V DC for L+ and 230 V AC for L1.

3. What output current should be verified for signal "1"?

The rated output current is 2 A, and the minimum load current is 10 mA.

4. Does the module provide short-circuit protection or diagnostics?

It has no short-circuit protection, alarms, diagnostics function, wire-break diagnosis, or short-circuit diagnosis.

Send Inquiry