6AG1322-1HF10-2AA0

Siemens SIPLUS S7-300 6AG1322-1HF10-2AA0 spare part with 8 isolated relay outputs, 24 V DC coil supply, and 5 A output current. Request a model-specific quote.

Product Code
6AG1322-1HF10-2AA0
Dimensions
13 × 15 × 5 cm
Weight
0.37 kg
Lifecycle
Product cancellation
Availability
in stock
Lead Time
Confirmed with quotation
Product Attachment
Download Datasheet
Request Current Quote

Current status: in stock. Price, condition, lead time and warranty are confirmed in the quotation.

Product Overview

Technical Summary

Parameter Value
Module type Digital output module with relay outputs
Digital outputs 8; Relays
Connection 1x 40-pole
Relay coil supply 24 V DC
Rated output current 5 A for signal "1"
Load voltage 120 V DC (L+); 230 V AC (L1)
Contact switching capacity 8 A resistive; 3 A inductive
Channel potential separation Yes; in groups of 1
Backplane bus separation Yes; Optocoupler
Isolation test 2 000 V AC
Operating cycles 300 000 max.

Applications

  1. Digital output control: Controls digital outputs through 8 relay channels.
  2. Digital input control: Can control a digital input.

Key Features

  1. Digital relay outputs: 8 digital relay outputs with potential separation between channels and between the outputs and the backplane bus.
  2. Load voltage: Rated load voltage: 120 V DC for L+ and 230 V AC for L1.
  3. Output current: Rated output current for signal "1": 5 A; minimum load current: 5 mA.
  4. Relay switching capacity: Contact switching capacity is up to 8 A with resistive load and up to 3 A with inductive load.
  5. Connection and isolation: 1x 40-pole connection; plugs with spring-loaded terminals can be used from 6ES7392-1BM01-0AA0. Isolation is tested with 2 000 V AC.
  6. Protection and diagnostics: Short-circuit protection must be provided externally. No alarms or diagnostics function are available; a digital-output status LED is provided.

Frequently Asked Questions

1. How many relay outputs does 6AG1322-1HF10-2AA0 have?

It has 8 digital relay outputs.

2. What output current does this module provide?

The rated output current for signal "1" is 5 A, with a minimum load current of 5 mA.

3. What connection does the module use?

It uses 1x 40-pole connection. Plugs with spring-loaded terminals can be used from 6ES7392-1BM01-0AA0.

4. Does the module include short-circuit protection or diagnostics?

Short-circuit protection must be provided externally. The module has no alarms or diagnostics function, but it has a digital-output status LED.